Collector Piping - American Water Heater SRCC OG-300 Instruction Manual

Residential solar water heating systems
Table of Contents

Advertisement

COLLECTOR PIPING

The piping of the system should be considered before a fi nal
decision is made on how the collectors are mounted. Piping
should be made of copper tube of the type meeting local
codes, insulated with Armacell UT Solafl ex or equivalent.
The maximum total piping length allowed in this system is
200 equivalent ft.
Use only lead-free solder. Use of 50/50 lead solder is
expressly prohibited. Use only type "L" or "M" copper
tubing in the collector loop plumbing. Use of galvanized
steel, CPVC, PVC, PEX or any other type of plastic pipe
is prohibited.
VERTICAL MOUNT
OUTLET
1" COPPER
CAPS
TEMPERATURE
SENSOR
AIR VENT
OUTLET
INLET
Figure 18.
1" COPPER
PIPE
HEADER
PIPE
SOLAR COLLECTOR
ADAPTER
COLLECTOR
(OUTLET)
Figure 19.
Care should be taken in the spacing of collectors as
attachment of piping is easiest with properly aligned
collectors. The connection between the collector panels is
made with copper unions or couplings. To aid in installation
the collector array layout should be planned on the ground
and the unions or couplings soldered to the adjoining
headers prior to lifting the collectors to the roof. Similarly
the top and bottom outside header that will not be used
for the inlet or outlet (should be on opposite sides) should
be capped with the 1" copper cap provided while on the
ground. See Figure 18.
HORIZONTAL MOUNT
1" COPPER
CAPS
19
COLLECTOR
(INLET)
INLET

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srcc og-100

Table of Contents