Connecting The Condensate Drain - Navien NHB-055 Installation & Operation Manual

Nhb series condensing boiler
Hide thumbs Also See for NHB-055:
Table of Contents

Advertisement

3.2 Connecting the Condensate Drain

The Navien NHB boiler creates condensation when it operates.
This condensation has an acidic pH of 3-5. Follow all local codes
and regulations when disposing of condensate from the boiler.
We recommend draining the condensate into a laundry tub,
as the alkali in laundry detergent will neutralize the acid in the
condensate. However, other suitable waste drain locations may be
used according to the local codes.
CAUTION
Do not cap or plug the integrated condensate line. If
prevented from draining, condensate can damage the boiler.
The condensate line must have a negative slope to drain
properly.
Before connecting the condensate drain, choose one of the
following disposal options:
a
a. From the boiler directly into an external drain.
Do not install a fixed connection for the drain.
Note
22
Installing the System Piping
c
d
b
b. From the boiler, through a neutralizing agent, and
then into an external drain (refer to "3.2.1 Condensate
Neutralizer Kit" on page 23).
If you choose this option, the neutralizing agent
Note
must be replaced periodically. Depletion of the
neutralizing agent will vary, based on the usage
rate of the boiler. During the first year of operation,
the neutralizer should be checked every few
months for depletion and replaced as needed.
c. From the boiler into a laundry tub.
The bottom of the boiler must be higher than
Note
the top of the laundry tub to use this option. The
condensate line must have a negative slope to
drain properly.
d. From the boiler into a condensate pump, and then into a
laundry tub.
A pump can be used when there is a long distance
Note
between the boiler and the laundry tub or when
the bottom of the boiler is lower than the top of the
laundry tub.
To connect the condensate drain:
1. Connect a drain line to the
boiler.
Use only corrosion-resistant material for the drain line, such as
PVC or CPVC. Do not reduce the size of this fitting or the drain
line to less than
/
in.
1
2
2. Place the free end of the drain line into an appropriate drain.
3. If you are using a condensate pump, ensure that the pump
allows for up to 2 GPH of drainage for each boiler in the
system.
4. If you are not using a condensate pump, ensure that the drain
line is pitched downward at a minimum slope of
/
in fitting at the bottom of the
1
2
NPT 1/2"
/
in per foot.