Toshiba RAV-SM2242DT-E Installation Manual page 17

Split type indoor unit concealed duct high static pressure type
Hide thumbs Also See for RAV-SM2242DT-E:
Table of Contents

Advertisement

6
If there is other indoor unit to be changed,
2
5
repeat procedure
to
to change the setup.
When the above setup has finished, push
to select the indoor UNIT No. before change of
setup, specify CODE No. [12], [13], [14] in order
with TEMP.
/
buttons, and then check the
changed contents.
Address change check Before change:
[3-3-1] → After change: [2-2-2]
Pushing
button clears the contents of which
setup was changed.
2
(In this case, procedure from
is repeated.)
Indoor UNIT No. before setup change is displayed.
7
After check of the changed contents, push
button. (Setup is determined.) When
pushing
button, the display disappears
and the status becomes the usual stop
status. (When pushing
button the
operation from the remote controller is not
accepted for approx. 1 minute.)
* If the operation from the remote controller is not
accepted even 1 minute or more passed after
pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup
1
change from the Procedure
.
31-EN
To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known
Check the position during operation stop.
(Be sure to stop operation of the set.)
1
2
1,3
1
Push simultaneously
+
buttons for
4 seconds or more.
After a while, the display part flashes and the
display appears as shown below.
In this time, the position can be checked because
fan of the indoor unit operate.
• For the group control, the indoor UNIT No. is
displayed as [
] and fans of all the indoor
units in the group control operate.
Check the displayed CODE No. is [01].
• When the CODE No. is other than [01], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the remote
controller is not accepted for approx. 1 minute.)
(* Display changes according to
the model No. of indoor unit.)
2
In the group control, every pushing
button, the indoor UNIT No. in the group
control is displayed in order.
In this time, the position of the indoor unit can be
confirmed because only fan of the selected indoor
unit operate.
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
3
After confirmation, push
button to return
the mode to the usual mode.
When pushing
button, the display disappears
and the status becomes the usual stop status.
(When pushing
button the operation from the
remote controller is not accepted for approx. 1
minute.)
– 16 –
8 °C operation
Pre-heating operation can be set for cold regions where room
temperature drops to below zero.
1
Push simultaneously
+
+
buttons
for 4 seconds or more when the air
conditioner is not working.
After a while, the display part flashes as shown
below. Check the Displayed CODE No. is [10].
• When the CODE No. is other than [10], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx. 1
minute.)
(* Display changes according to
the model No. of indoor unit.)
2
Every pushing
button, the indoor
unit No. in the group control is displayed in
order. Select the indoor unit of which setup
is changed. In this time, the position of the
indoor unit of which setup is changed can be
confirmed because fan of the selected
indoor unit operate.
3
Using TEMP.
/
buttons, specify
CODE No. [d1].
4
Using TIME
/
buttons, select SET
DATA [0001].
SET DATA
8 °C Operation setting
None
0000
(Factory default)
0001
8 °C Operation setting
5
Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
6
Push
button.(Setup is determined.)
When pushing
button, the display disappears
and the status
Becomes the usual stop status. (When pushing
button the operation from the remote controller
is not accepted for approx. 1 minute.)
EN
32-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm2802dt-e

Table of Contents