Refrigerant Piping Connection; Tightening Connection - Toshiba RAS-10(7)~16(7)SKV Series Installation Manual

Air conditioner (split type)
Table of Contents

Advertisement

Refrigerant Piping Connection

Flaring
1. Cut the pipe with a pipe cutter.
90
2. Insert a Á are nut into the pipe and Á are the pipe.
• Projection margin in Á aring : A (Unit : mm)
Rigid (clutch type)
Outer dia.
R410A tool used
of copper pipe
6.35
9.52
12.70
Imperial (wing nut type)
A
Outer dia. of copper pipe
Die
Pipe

Tightening connection

Align the centers of the connecting pipes and tighten the Á are nut as far as pos-
sible with your À ngers. Then tighten the nut with a spanner and torque wrench
as shown in the À gure.
Half union
Externally
threaded side
Use a wrench to secure.
CAUTION
Do not apply excess torque. Otherwise, the nut may crack depending on
the conditions.
Outer dia. of copper pipe
Ø6.35 mm
Ø9.52 mm
Ø12.70 mm
• Tightening torque of Á are pipe connections
The operating pressure of R410A
is higher than that of R22 (approx.
1.6 times). It is therefore necessary
to À rmly tighten the Á are pipe
connecting sections (which connect
the indoor and outdoor units) up to the
speciÀ ed tightening torque. Incorrect
connections may cause not only a
gas leakage, but also damage to the
refrigeration cycle.
Shaping pipes
1. How to shape the pipes
Shape the pipes along the incused line on
the outdoor unit.
2. How to À t position of the pipes
Put the edges of the pipes to the place with
a distance of 85 mm from the incused line.
Evacuating
After the piping has been connected to the indoor unit, you can perform the
air purge together at once.
1110251155-EN.indd 6
Obliquity
Roughness
Warp
Conventional tool
used
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
R410A
6.35
1.5 to 2.0
9.52
1.5 to 2.0
12.70
2.0 to 2.5
Flare nut
Internally
threaded side
Use a torque wrench to tighten.
(Unit : N·m)
Tightening torque
16 to 18 (1.6 to 1.8 kgf·m)
30 to 42 (3.0 to 4.2 kgf·m)
50 to 62 (5.0 to 6.2 kgf·m)
Flare at
indoor unit side
Flare at
outdoor unit side
Incused line
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a
vacuum pump. Do not use the refrigerant in the outdoor unit. For details,
see the manual of the vacuum pump.
Using a vacuum pump
Be sure to use a vacuum pump with counter-Á ow prevention function so that
inside oil of the pump does not Á ow backward into pipes of the air conditioner
when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R410A,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to the service port of the
packed valve at gas side.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for
about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute) Then conÀ rm that the
compound pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of the gauge manifold valve.
6. Open fully the valve stem of the packed valves (both gas and liquid sides).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
–101 kPa
(–76 cmHg)
Handle Lo
Charge hose
(For R410A only)
Connecting pipe
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING WORK.
(1) Take away dust and moisture (inside of the connecting pipes).
(2) Tighten the connections (between pipes and unit).
(3) Evacuate the air in the connecting pipes using a VACUUM PUMP.
(4) Check gas leak (connected points).
Packed valve handling precautions
• Open the valve stem all the way out, but do not try to open it beyond the
stopper.
• Securely tighten the valve stem cap with torque in the following table:
Gas side
50 to 62 N·m
(Ø12.70 mm)
(5.0 to 6.2 kgf·m)
Gas side
30 to 42 N·m
(Ø9.52 mm)
(3.0 to 4.2 kgf·m)
Liquid side
16 to 18 N·m
(Ø6.35 mm)
(1.6 to 1.8 kgf·m)
9 to 10 N·m
Service port
(0.9 to 1.0 kgf·m)
Wiring Connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminals as identiÀ ed with their
respective matched numbers on the terminal block of indoor and outdoor
unit.
3. When connecting the connecting cable to the outdoor unit terminals, make
a loop as shown in the installation diagram of indoor and outdoor unit to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the
outdoor unit. Proceed them so that they do not touch any electrical or metal
parts.
6
EN
ES
FR
IT
DE
Pressure gauge
PT
Manifold valve
Handle Hi
(Keep full closed)
PL
Charge hose
(For R410A only)
CZ
Vacuum pump adapter for
counter-Á ow prevention
(For R410A only)
RU
Vacuum
pump
CR
HU
TR
NL
GR
SV
FI
NO
The hexagon wrench
is required.
DK
RO
BG
EE
LV
SK
SI
12/18/07 3:47:28 PM

Advertisement

Table of Contents
loading

Table of Contents