Installation and User Manual Infinity 20e Infinity 20e Continuous Flow Water Heater Important. Read these instructions carefully before attempting installation or use of this appliance. All work must be carried out by competent persons.
65 C and do not include installations incorporating storage cylinders or building flow and return systems. The warranty shall apply to any Rinnai water heater from the Infinity range used in this way. Definition of Commercial Use.
UNPACKING RINNAI WATER HEATER • After unpacking the appliance check for damage, if the heater is damaged contact your supplier immediately. Do not install a damaged appliance before checking with your supplier. • One remote control and heater accessories pack are inside the carton.
INSTALLATION INSTRUCTIONS IMPORTANT INFORMATION 1. Gas safety (Installation & Use) regulations 1998 are the ‘Rules in force’. In your own interest and that of safety, it is law that all gas appliances are installed by competent persons in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution.
Page 6
Multiple heater installations can be installed with the heaters manifolded together. The heater draws combustion air through the casing for the external model. Heater guards and pipe cover boxes for security and safety are available from Rinnai.
Page 7
1 mg/litre Levels Gas Connection Check pipe sizing required for the heater input. The heat input for the Infinity 20e is 44.4 kW. Refer to BS6891 (Natural Gas) and BS5482 (Propane) for guidance on correct pipe sizing calculation. Check that the size of the gas meter and pipework will be sufficient for all appliances on the main.
FLUE REQUIREMENTS - POSITIONING Dimension Terminal Position Distance Directly below an opening, air brick, opening windows, etc. 300mm Above an opening, air brick , opening window, etc. 300mm Horizontally to an opening, air brick , opening window, etc. 300mm Below gutters, soil pipes or drain pipes. 75mm Below eaves.
TECHNICAL DETAILS Infinity Model Infinity 20e Units Installation External Nat Gas Press Low mbar Nat Gas Press High mbar LPG Press Low mbar LPG Press High mbar Height Width Depth Weight Flue System Forced Exhaust Temp. Range Controllers 37 - 75 deg C Temp.
Congratulations on purchasing the Technologically Advanced, Temperature Controlled, Rinnai Hot Water System. The Rinnai Infinity 20e NEVER RUNS OUT of hot water. As long as electricity, • water, and gas supplies are connected, hot water is available when hot water taps are open.
Do make sure that the tap is turned off tightly. This approach can be extremely valuable because it requires a Do consider setting your Rinnai one time action for a long term Infinity 16e at a maximum reduction in risks of scalds.
Page 13
Refer to warning about hot water on page 12 for important safety information. The Infinity 20e controls the water If freezing temperatures temperature automatically. For high are expected, turn off the temperatures it may reduce the flow. The...
Turn On by opening the hot water tap Rinnai Infinity water heaters without controllers are factory pre-set to a temperature limit of 55°C. Other limits, lower or higher, are available on request for the Infinity range.
Page 15
TEMPERATURE CONTROLS - GENERAL When deciding on the best position for the temperature controls, the following points should be taken into account. Fit the controls out of reach of children (suggested height from the floor 1.5m.) • Avoid positions where the controllers will become hot. Do not fit them near stoves or •...
Page 16
TEMPERATURE CONTROLS - INSTALLATION Universal Temperature Controller MC-91-1A 1. Determine the most suitable position for the temperature controller. 2. Drill 3 holes in the wall as shown in fig. 1, one for the cable and two for the securing screws. Ensure holes are drilled deep enough.
Page 17
TEMPERATURE CONTROLS - INSTALLATION Connecting One or Two Controllers 1. Isolate the power supply. 2. Remove the front cover from the Appliance (4 screws) fig. 1. 3. Thread the cable through the cable access hole at the base of the appliance. 4.
To obtain water temperatures lower than 37°C simply add cold water. Up to three controllers can be used for one Infinity 20e. When multiple temperature controllers are used they allow the temperature to be set from various locations by pushing the transfer button which gives that controller priority over the system.
TEMPERATURE CONTROLS - OPERATING Remote temperature controllers are a feature that provides control over the water temperature. Rinnai Infinity water heaters can be operated with 1, 2, 3 or no temperature controllers. The Universal controller MC-91-1A comes as standard with all Infinity water heaters.
Page 20
TEMPERATURE CONTROLS - OPERATING Using 1 Universal Temperature Controller. Press the On/Off button on the temperature controller. The ON indicator will glow on the Temperature Controller. This indicates that the heater is ready to supply hot water when a tap is opened. Adjusting Temperature Simply press the Hot Water Temperature Up or Down arrow button until the desired temperature is displayed on the...
Page 21
TEMPERATURE CONTROLS - OPERATING Using 2 or more Universal Temperature Controllers. Switching the system ON. The hot water system and all controllers can be switched ON and OFF from any controller by pressing the On/Off button as shown. When the system is turned ON the water temperature display will be lit.
Page 22
TEMPERATURE CONTROLS - OPERATING Using High Temperature Display Controllers. You will need to program the Master controller if you want to display and use temperatures over 50 C. Programming only needs to be done on Master universal controllers; other universal controllers will not allow this, and Deluxe Kitchen Controllers are supplied already programmed to allow high temperatures.
Page 23
The on indicator will go out. If hot water taps are opened when the Rinnai Infinity is off, cold water will flow from the taps. If the system is to be left off over the winter be sure to drain it down if there is a possibility of freezing temperatures.
Page 24
TEMPERATURE CONTROLS - INFORMATION Do not push the On/Off button on the Temperature priority can not be switched Master controller after transferring priority to another controller when the water is of temperature selection to a Secondary flowing through the water heater. controller as the system will shut down.
TESTING 1. Purge gas, hot water and cold water supply lines before making the final connection of the water heater. Swarf in either the gas or water supplies may cause damage. 2. Turn on gas and cold water supplies. 3. Test for water leaks and gas escapes near the unit. 4.
Under normal circumstances it does not require adjustment during installation. Perform this procedure only if the unit is not operating correctly and all other possible causes for Contact Rinnai UK before incorrect operation have been eliminated. attempting to alter the gas pressure. Failure to do so could void the warranty.
Page 27
GAS PRESSURE SETTING 11.Remove rubber access plug and adjust the regulator screw on the modulating valve (fig. 4) as required to the pressure below. 1.8 mbar Propane 1.9 mbar 12.Lock the regulating screw on the modulating valve. 13.Set the appliance to 'Forced High' combustion by setting both no.
GAS TYPE NAT GAS OFF ON SW2 OFF ON SW2 COMPUTER PROGRAMMING OFF ON SW1 Switches are always in these positions for the Infinity 20e. COMBUSTION NORMAL FORCED LOW FORCED HIGH OFF ON SW1 OFF ON SW1 OFF ON SW1...
Page 29
DIP SWITCH SETTING Infinity 20e Temperatures - With or Without Remotes on SW2 on SW2 on SW2 40 deg C 43 deg C 50 deg C on SW2 on SW2 on SW2 55 deg C 65 deg C 75 deg C...
* In all cases, you may be able to clear the Error code by turning the hot water tap OFF, then ON again. If this does not clear the error, try pushing the On/Off button OFF then ON again. If the Error Code still remains contact Rinnai or your nearest service agent for advice.
Page 31
ERROR MESSAGES Troubleshooting without controllers If you have not installed temperature controllers and experience the following symptoms, please carry out the suggestions below. If symptoms continue, please contact Rinnai for advice. Fault Remedy Heater does not attempt Check the power is on at the heater.
If following the above procedure does not reset the heater switch it on and off at its main supply, and then go through these steps again. If heater is still not working call your local service agent or Rinnai for assistance.
Electrical Supply…………………………….…………..……………….230V AC 50Hz 1ph * Separate models available for Natural gas or LPG fuel. ** Minimum flow rate based on temperature setpoint and inlet conditions. Rinnai are continually updating and improving products and reserve the right to alter model specifications without prior notice.
SERVICE CONTACT Rinnai Rinnai UK LTD. 9 Christleton Court Manor Park Runcorn Cheshire WA7 1ST Tel. 01928 531870 Fax. 01928 531880 E-mail. info@rinnaiuk.com Web. www.rinnaiuk.com...
Page 37
INFINITY 16 e INFINITY 20 e SERVICE MANUAL Rinnai High Capacity Continuous Flow Gas Hot Water System Service Manual Infinity 16e and 20e Service Manual Infinity 16e and 20e...
Page 38
Quality System Standard ISO 9001 - 1994 The Design, Development, and Manufacture of Gas Water Heating Appliances done under Rinnai’s Quality Management System is certified under the Quality Management System Standard ISO 9001. Registration Number JQ0003D Registered since: February 1994 Certified by Japan Gas Appliances Inspection Association.
Page 39
Produced by Rinnai Technical Services Department August 2004 - Issue 1. No portion or part of this manual may be copied without prior permission from Rinnai U.K. Rinnai U.K. reserves the right to make modifications and change specifications without notice.
1. Introduction The Rinnai V-Series hot water units represents the latest technology in continuous flow, temperature controlled hot water. Features • The Infinity 16e and Infinity 20 NEVER RUNS OUT of hot water. Whilst electricity, water and gas supplies are connected, hot water is available whenever hot water taps are open.
2. Specifications Note 1: The default factory setting is 55º C for 16e. The unit can be ordered from Rinnai to be pre-set to any of the other temperatures listed. The unit can be pre-set to any of the temperatures listed by a suitably qualified person.
Page 44
Note 1: The default factory setting is 55° C for Infinity 20e. The unit can be ordered from Rinnai to be pre-set to any of the other temperatures listed. The unit can be pre-set to any of the temperatures listed by a suitably qualified person.
Controllers are supplied with 15 m of electrical cable. The cable wires for connection to the appliance are fitted with spade terminals. Extension cables are available from Rinnai. Alternatively, a two core sheathed (double insulated) flex with minimum cross-sectional area of 0.5 mm² can be used. Maximum cable length is 50 m.
10. Time Charts Normal Combustion Mis-Ignition / Flame Failure Abnormal Pre-Purge (Air Supply/Exhaust Blockage) Service Manual Infinity 16e and 20e Service Manual Infinity 16e and 20e REU-V1616W/REU-V2018W/REU-V2020W - 18 - Rinnai...
SERVICE CONTACT POINTS Rinnai Rinnai UK LTD. 9 Christleton Court Manor Park Runcorn Cheshire WA7 1ST Tel. 01928 531870 Fax. 01928 531880 E-mail. info@rinnaiuk.com Web. www.rinnaiuk.com Service Manual Infinity 16e and 20e Service Manual Infinity 16e and 20e Infinity 32e and HD70e...