Page 1
INFINITY 26i and HD50i SERVICE MANUAL Infinity High Capacity Continuous Flow Gas Hot Water System...
Page 2
Quality System Standard ISO 9001 - 1994 The Design, Development, and Manufacture of Gas Water Heating Appliances done under Rinnai’s Quality Management System is certified under the Quality Management System Standard ISO 9001. Registration Number JQ0003D Registered since: February 1994...
Page 3
Produced by Rinnai Technical Services Department August 2004 - Issue 1. No portion or part of this manual may be copied without prior permission from Rinnai U.K. Rinnai U.K. reserves the right to make modifications and change specifications without notice.
Features • The Infinity 26i and HD50i NEVER RUN OUT of hot water. Whilst electricity, water and gas supplies are connected, hot water is available whenever hot water taps are open. • Built into the main micro-processor is the facility to LIMIT THE MAXIMUM TEMPERATURE of the hot water supplied.
Note 1: The default factory setting is 55ºC for the Infinity26i, and 65°C for HD50i. The unit can be ordered from Rinnai to be pre-set to any of the other temperatures listed. The unit can be pre-set to any of the temperatures listed by a suitably qualified person.
Controllers are supplied with 15 m of electrical cable. The cable wires for connection to the appliance are fitted with spade terminals. Extension cables are available from Rinnai. Alternatively, a two core sheathed (double insulated) flex with minimum cross-sectional area of 0.5 mm² can be used. Maximum cable length is 50 m.
12. Dip Switch Settings WARNING: Dip Switch settings must only be changed by an authorised person. Dip Switch Settings for Infinity 26i and HD50i Dip Switch Settings for Infinity 26i and HD50i Note: Unit must be specially converted for delivery at 85 C for REU-V2632FFUC models only.
Page 27
Check water flow servo not controlled, temp too low Solenoid valve circuit error. Unit Check Gas Valves are open visual does not operate Check Solenoids Flame Rod Circuit Error. Unit does Check Flame Rod not operate Infinity 26i and HD50i...
Page 28
Check anti frost heater components operate. Check frost sensing switch Check Gas Supply is correct Upon commissioning the gas Check Gas Filter pressure will not achieve correct Check flue terminal for blockages visual high pressure Check Flue Infinity 26i and HD50i...
Page 29
1 M Ohm (1000 k Ohms) If this is not correct replace the sparker box / sub pcb. If this is correct, but the electrode is not sparking then visually inspect the electrode, clean it, set the gap, or replace it. Infinity 26i and HD50i...
Page 30
Current should be over 1 micro (µ)Amp If current is more than this the pcb is faulty. If current is less than this the flame rod is faulty or needs cleaning. Infinity 26i and HD50i...
Page 31
If the resistance is greater than 1 Ohm test each individual sensor to find which one is faulty and replace it AFTER checking the heater for damage. Check that the gas type and combustion dip switch settings are correct. Confirm gas pressure when the unit is operating again. Infinity 26i and HD50i...
Page 32
If one of the servos is not operating correctly it is probably the servo motor, but could potentially be the pcb. Continue on. Infinity 26i and HD50i...
Page 33
Brown – White 2 – 6 Vdc Orange – White 2 – 6 Vdc Yellow – White 2 – 6 Vdc Red – White 2 – 6 Vdc If these values are incorrect replace the bypass servo. Infinity 26i and HD50i...
Page 34
If Black – Red is incorrect replace pcb If Yellow – Black is incorrect replace water flow sensor. Before you replace the water flow sensor be sure you have checked the filter (R) and for air locks (M). Infinity 26i and HD50i...
Page 35
This thermistor is located in the combustion air fan. To find it the first time you may need to remove the combustion air fan. Do not pull the fan out too quickly or you will ruin the thermistor. Infinity 26i and HD50i...
Page 36
If there is no power at this point you must find where the connection has been lost. O. 3 Amp Fuses The unit has two inline 3 Amp fuses. Remove the fuse and check for continuity through. If there is continuity the fuse is good, if not replace it. Infinity 26i and HD50i...
Page 37
It holds a small micron basket strainer. The strainer becomes clogged easily, especially after installation. When it is clogged sometimes water will travel through the unit without triggering the flow sensor. Make sure you check any external Y- strainers as well Infinity 26i and HD50i...
Page 38
S. Water flow. To operate there must be at least 2.4 l/min flowing through a Rinnai water heater. If there is multiple heaters, installed without PAM valves or a MECS system then there must be 2.4 l/min per heater. A modern wash hand basin could be as low as 3 or 4 l/min, so if there is no means of staging the heaters they may not operate.
Page 39
9m. If there is a condensate trap installed, be sure it is the right way up (with the male section at the bottom.) Infinity 26i and HD50i...
Page 41
17. The maintenance number will be shown in the Water Temperature display. 18. Data will be shown in the Clock display. 19. To select the required maintenance number, press the Water Temperature "UP" and "DOWN" buttons. Note: Infinity 26i and HD50i use Maintenance Numbers 1-12. Display Monitor Contents Contents Units...
Page 49
Anti Frost Heater Installation Anti Frost Heaters come as standard on ALL Rinnai Infinity and Heavy Duty water heaters sold in the UK. They will not need to be installed on site. The diagram on the following page shows where the elements are located.