MH SERIES INSTALLATION INSTRUCTIONS
D. PRE-INSTALLATION PREPARATION
1. Fireplace Locations and Space Requirements
Several options are available to you when choosing a location for your fireplace. This fireplace may be used as a
room divider, installed along a wall or across a corner. See Figure 2.
Locating the fireplace in a basement, near frequently opened doors, central heat outlets or returns, or other locations
of considerable air movement can affect the performance and cause intermittent smoke spillage from the front of the
fireplace. Consideration should be given to these factors before deciding on a location.
Figure 2 - Fireplace Locations
Figures 3 and 4 show two typical installations assuming an outside air kit is being used. Therefore, an allowance
must be made for 90-deg bends. Less space is required when ducting goes directly outside without forming
elbows.
Figure 3
Installation Along a Wall
Figure 4 - Corner Installation
Do not draw outside air from garage spaces. Exhaust products of gasoline engines are hazardous.
Do not install outside air ducts such that the air may be drawn from attic spaces, basements or above the
roofing where other heating appliances or fans and chimneys exhaust or utilize air. These precautions will
reduce the possibility of fireplace smoking or air flow reversal.
To prevent contact with sagging or loose insulation, the fireplace must not be installed against vapor barriers
or exposed insulation. Localized overheating could occur and a fire could result.
08/04
A minimum 1/2 in. air clearance must
be maintained at the back and sides
of the fireplace assembly.
Chimney sections at any level require
a 2 in. minimum air space clearance
between the framing and chimney
section.
Without Outside Air
Cat. #
A
MH36A
42 in.
MH39A
45 in.
MH42A
48 in.
These are rough framing
dimensions only.
With Outside Air
Cat. #
A
B
MH36A 42 in.
72-3/4 in.
MH39A 45 in.
75-3/4 in.
MH42A 48 in.
78-3/4 in.
WARNING!
WARNING!
17804 Rev i
CLEARANCES!
With Outside Air
Cat. #
A
MH36A
42 in.
MH39A
45 in.
MH42A
48 in.
C
D
E
36-3/8 in.
15-5/8 in. 51-3/8 in.
37-7/8 in.
6-5/8 in.
53-1/2 in.
9-3/8 in.
17-5/8 in. 55-3/8 in.
9