Fault Display; Fault Codes - Viessmann Vitodens 200-W Service Instructions Manual

Wall-mounted, gas-fired condensing boiler for operation with natural gas heating input 104 to 352 mbh 30 to 103 kw
Table of Contents

Advertisement

Troubleshooting

Fault Display

In the event of a fault, red fault indicator A flashes.
"
" flashes on the display and "Fault" is shown.
The fault code is displayed with OK. For an explanation
of the fault code, see the following pages.
For some faults, the type of fault is also displayed in
plain text.

Fault Codes

Fault code on display
0F
10
18
1A
NOT USED
1B
NOT USED
1F
NOT USED
20
28
30
38
*1
Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
70
PSI
System behavior*1
Control mode
Boiler operates based on outdoor
temperature of 32°F (0°C)
Boiler operates based on outdoor
temperature of 32°F (0°C)
Burner blocked
Burner blocked
Burner blocked
Regulates without supply
temperature sensor
(low-loss header)
Regulates without supply
temperature sensor
(low-loss header)
Burner blocked
Burner blocked
Vitodens 200-W B2HA 80, 100 Service
Acknowledging a fault
Follow the instructions on the display.
Note: The fault message is transferred to the standard
menu. A fault message facility, if connected, will
be switched OFF. If an acknowledged fault is not
remedied, the fault message will be re-displayed
the following day and the fault message facility
restarted.
Calling up acknowledged faults
Select "Fault" in the standard menu.
The current faults will be displayed in a list.
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults (including resolved ones) are
saved and can be called up.
Faults are sorted by date.
1. Press OK and
simultaneously for approximately
4 seconds.
2. "Fault history"
3. "Display?"
Cause
Code "0F" is only
displayed in the fault
history
Short circuit on outdoor
temperature sensor
Outdoor temperature
sensor cable broken
Flow sensor 1 faulty
Flow sensor 2 faulty
Differential flow rate
too large
Short circuit on system
flow temperature sensor
System supply
temperature sensor
cable broken
Short circuit on boiler
water temperature
sensor
Boiler water temperature
sensor cable broken
Corrective action
Service required
Note: After servicing select
code "24:0"
Check the outdoor temperature
sensor (see page 78).
Check the outdoor temperature
sensor (see page 78).
Replace sensor (see page 79)
Replace sensor (see page 79)
Clean heat exchanger by
flushing
Check the low-loss header
sensor (see page 79).
Check the low-loss header
sensor (see page 79). If no
low loss header sensor is
connected, set code 52:0.
Check the boiler water
temperature sensor
(see page 79).
Check the boiler water
temperature sensor
(see page 79).