Boiler - Viessmann Vitodens 200-W Service Instructions Manual

Wall-mounted, gas-fired condensing boiler for operation with natural gas heating input 104 to 352 mbh 30 to 103 kw
Table of Contents

Advertisement

Coding 2

Boiler

Select "Boiler"
Coding
Coding in the factory setting
01:1
04:1
06:...
07:1
08:...
0D:0
0E:0
13:1
14:1
15:1
21:0
23:0
24:0
28:0
2E:0
2F:0
30:0
31:...
NOT USED
38:0
54
Single boiler system
Minimum burner pause subject
to the boiler load (specified by
boiler coding card)
Maximum limit of the boiler
water temperature, specified
in °C by the boiler coding card
Boiler number in multi boiler
systems
Maximum burner heating output
in kW in the case of a multi
boiler system
DO NOT ADJUST
DO NOT ADJUST
DO NOT ADJUST
DO NOT ADJUST
DO NOT ADJUST
No service interval (hours run)
selected
No time interval for burner
service
No "Service" display
No burner interval ignition
DO NOT ADJUST
Venting program/fill program
disabled
Coding address should be set
to 30:0, if not adjust to 30:0
Set speed in % of the internal
circulation pump when operated
as boiler circuit pump, specified
by the boiler coding card
Status burner control unit:
Operational (no fault)
Vitodens 200-W B2HA 80, 100 Service
Possible change
01:2
Multi boiler system with Vitotronic
300-K.
04:0
Minimum burner pause set
permanently (specified by boiler
coding card).
06:20
Maximum limit of the boiler water
to
temperature within the ranges
06:127
specified by the boiler.
07:2
Boiler number 2 to 8 in multi-
to
boiler systems.
07:8
08:0
Maximum burner heating output
to
adjustable from 0 to 199 kW
08:199
(limited by boiler specific
parameters) in steps of 1 kW.
--
--
--
--
--
21:1
Number of hours run before the
to
burner should be serviced is
21:100
adjustable from 100 to 10,000 h
One adjusting step ≙ 100 h.
23:1
Interval adjustable from 1 to 24
to
months.
23:24
24:1
"Service" display (the address is
automatically set and must be
manually reset after a service has
been carried out).
28:1
Interval adjustable from 1 hour
to
to 24 hours. The burner is force
28:24
started once every 30 seconds
(only when operating with LPG).
--
2F:1
Venting program enabled.
2F:2
Fill program enabled.
30:3
When changing from a single boiler
to a multiboiler operation, the
coding address may automatically
reset to 30:3. To prevent
continuous boiler pump operation,
adjust the coding address for each
boiler to 30:0.
31:0
Set speed adjustable from
to
0 to 100%.
31:100
38:≠0
Status burner control unit: Fault.
--
--
--
--
--
--