Viessmann Vitodens 200-W Installation Instructions Manual page 62

4.8 to 35.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Combustion
If the actual CO
2
the following steps:
• Check the balanced flue system for soundness, see page 66
• Check the ionisation electrode and connecting lead, see service instructions.
• Check the parameters of the combustion control unit, see service instructions.
Note
During commissioning, the combustion control unit carries out an automatic calibration. This
may lead to CO emissions in excess of 1000 ppm for a short time.
1. Connect a flue gas analyser at test port
A
(on the boiler flue outlet).
2. Open the gas shut-off valve, start the
boiler and create a heat demand.
3. Adjust the lower output of the
constant temperature control unit:
+
press simultaneously:
OK
"1" is shown
62
or O
values lie outside their respective ranges, proceed with
2
4. Check the CO
content. Should the
2
actual value deviate from the above
ranges by more than 1%, implement
steps above.
5. Enter actual values into the service
report.
6. Adjust the upper output on the
constant temperature control unit:
+
press: "2" is shown
7 . Check the CO
content. Should the
2
actual value deviate from the above
ranges by more than 1%, implement
steps above.