3.7.3 Battery over current protection and wire sizing

NOTE !
Please read the safety precautions at the front of this guide carefully, and
thoroughly review the battery manufacturers installation and maintenance
manual before connecting the batteries to the UPS.
The remote rack mounted batteries are to be used then DC over current
protection must be provided by others.
Choose an appropriate DC fuse or circuit breaker using the current data in the
chart below.
Minimum battery cable requirement is based on the current data below.
The maximum available fault current from the battery supply is: 20kA.
The minimum breaker voltage rating is 540V
These maximum and nominal ratings should be considered when choosing the appropriate AC
NEC (National Electric Code) Section 210-20 (A) rules must be applied.
DC current rating is the nominal battery discharge current which the UPS allows.
UPS rating
Nom.
SG Series 400
512 A
SG Series 500
617 A
Size of Branch Circuit Over Current Protection - All Models: - "CAUTION - To reduce the risk of fire,
only connect UPS to a circuit provided with (See below) maximum amperes branch circuit over
current protection in accordance with the NEC (National Electric Code), NSI / NFPA 70
AC Input Rectifier
UPS rating
SG Series 400
SG Series 500
UPS rating
Rectifier Input
SG Series 400
4x500 kcmil
SG Series 500
Modifications reserved
OPM_SGS_ISG_M40_M50_2US_V021.doc
The AC values below are current ratings per phase.
over current protection device.
(See Fig. 3.7.1-1 and 3.7.1.2)
AC Input Rectifier
F1
Max.
615 A
708 A
AC Input Bypass
F1
800 A
1,000 A
Wire sizing according to
NEC Section 210-20 (A)
Use 167°F (75°C) copper wire
Wiring requirements:
AC INPUT RECTIFIER:
AC INPUT BYPASS:
AC OUTPUT:
DC INPUT:
Maximum recommended cable size
Bypass Input
4x500 kcmil
AC Input Bypass
F2
Nom.
481 A
512 A
600 A
617 A
AC Input
F2
700 A
800 A
800 A
1,000 A
WIRING
Table 310-16
3-Phase, 3 wire plus Ground
3-Phase, 4 wire plus Ground
3-Phase, 4 wire plus Ground
2 wire (positive and negative) plus Ground
DC Input
4x600 kcmil
AC Input
F3
Max.
615 A
708 A
DC Input
F3
F4
1,000 A
1,200 A
AC Output
4x500 kcmil
3x500 kcmil
User Manual SG Series 400 & 500 UL S2
DC Input
F4
702 A
960 A
GND
Page 20/41