Installation Instructions for
Honeywell ALL-SPEC Air Sampling Smoke Detection System
1
Operating indicator light
2
Alarm indicator light for detector
module II
3
Alarm indicator light for detector
module I
4
Indicator light for common fault
5
Pre-punched cable entries for connection to the central fire panel or power supply (input/output)
6
Connection pipe system I
7
Connection pipe system II
8
Connection for air return
ALL-SPEC_Unit_HON.doc
1
2
3
4
07/2011
7
6
5
5
8
5
1/9

Advertisement

loading

Summary of Contents for Honeywell ALL-SPEC

  • Page 1 Installation Instructions for Honeywell ALL-SPEC Air Sampling Smoke Detection System Operating indicator light Alarm indicator light for detector module II Alarm indicator light for detector module I Indicator light for common fault Pre-punched cable entries for connection to the central fire panel or power supply (input/output)
  • Page 2: Installation Of The Detector Module

    Installation of the Detector Module Please note: Only the detector modules of the type ASD-TP-05, ASD-TP-01 and ASD-TP-001 that have been approved by the VdS-certification authority with the approval number G 202064 may be used. 1. Carry out the following works only if the device is powered down. 2.
  • Page 3 Detector Module Settings In the following tables the switch S1 has two positions: The standard settings have a grey background. Setting the response sensitivity detector module DM-TP- DM-TP- DM-TP- 0,8 %/m 0,12 %/m 0,4 %/m 0,06 %/m 0,2 %/m 0,03 %/m 1,0 %/m 0,5 %/m 0,1 %/m...
  • Page 4 HEAD 1 DIAG HEAD 2 DISPLAY X5 2 1 Choose number of the detector modules The number of fitted detector modules are chosen with the jumper JU4. The following table shows, whether the jumper must be put or not: X = pin pair bridge O = pin pair open The standard settings have a grey background.
  • Page 5 Setting the function of the fault contact The contact type (break contact or make contact) of the collective fault is set using the jumper JU 2 and JU 3. Fault contact detector module I = Jumper JU2 Fault contact detector module II = Jumper JU3 The following table shows the positioning of the jumpers: X = pin pair bridge O = pin pair open...
  • Page 6: Installation Of The Device

    Installation of the device General information: - When choosing the installation location make sure the displays of the device are clearly visible. - Screw the air sampling smoke detection system either directly to the wall with its bottom casing or mount it by means of a special support (type MT-1).
  • Page 7 internal connection base board 24 V +24V +24V DJ 1191 DJ 1192 connection to central fire panel connection to central fire panel DJ 1191 DJ 1192 connection to central fire panel connection to central fire panel Connection contact of the first alarm relay (make contact) X6, 1 centre tap of first alarm relay contact of the first alarm relay (break contact)
  • Page 8 Flow-Init Commissioning 1. Make sure first that the device has been in operation for at least 30 minutes prior to the air flow initialization in order to reach the operating tem- perature. 2. In order to initialize the connected pipe system, press the Flow-Init-button S2 (see figure) of the corresponding detector module until the green operating indicator light of the device starts flashing.
  • Page 9 Class: A, B and C 0,1 % light obscuration/m Class: A, B and C 0,5 % light obscuration/m Class: A, B and C Honeywell Life Safety Systems 140 Waterside Road Hamilton Industrial Park Leicester LE5 1TN (+44) 116 246 2000 ALL-SPEC_Unit_HON.doc...