TECHNICAL GUIDE
AFFINITY
MODELS: PS8*UH
GAS-FIRED
HIGH EFFICIENCY SINGLE STAGE
UPFLOW/HORIZONTAL FURNACES
STANDARD & Low NOx
80% AFUE
NATURAL GAS
40 - 130 MBH INPUT
EFFICIENCY
RATING
CERTIFIED
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
These high efficiency, compact units employ induced com-
bustion, reliable hot surface ignition and high heat transfer
aluminized tubular heat exchangers. The units are factory
shipped for installation in upflow or horizontal applications.
These furnaces are designed for residential installation in a
basement, closet, alcove, attic, recreation room or garage
and are also ideal for commercial applications. All units are
factory assembled, wired and tested to assure safe depend-
able and economical installation and operation.
These units are Category I listed and may be common
vented with another gas appliance as allowed by the
National Fuel Gas Code.
WARRANTY
20-year limited warranty on the heat exchanger.
10-year heat exchanger warranty on commercial applica-
tions.
5-year limited parts warranty.
FEATURES
• Compact, easy to install, ideal height 40" cabinet.
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement applica-
• Integrated control module for reliable, economical opera-
• Electronic Hot Surface Ignition saves fuel cost with
• Induced combustion system with inshot main burners for
• 100% shut off main gas valve for extra safety.
• Multi-speed PSC, large, quiet direct-drive blower motor to
• 24V, 40 VA control transformer and blower relay supplied
• Hi-tech tubular aluminized steel primary heat exchanger.
• Timed on, adjustable off blower capability for maximum
• Solid removable bottom panel allows easy application.
• Easy access from front of unit for cleaning, maintenance
• Insulated blower compartment for quiet operation.
• Independent door removal for greater durability and ease
ISO 9001
Certified Quality
Management System
• Low NOx models have been designed to meet specific
• All models are propane convertible.
tion.
tion.
increased dependability and reliability.
quiet, efficient operation.
match cooling requirements.
for add-on cooling.
comfort.
or service.
of access.
code requirements.
278432-YTG-A-0407

Advertisement

Table of Contents
loading

Summary of Contents for York AFFINITY PS8*UH

  • Page 1 Due to continuous product improvement, code requirements. specifications are subject to change without notice. • All models are propane convertible. Visit us on the web at www.york.com for the most up-to-date technical information. Additional rating information can be found at www.gamanet.org.
  • Page 2: Cabinet And Duct Dimensions

    278432-YTG-A-0407 4” Diameter (VENT CONNECTIONS) POWER WIRING 7/8” HOLE 14-3/4 13-3/4 5-3/8 2-1/2 32-1/2 GAS INLET ACCESS 1-1/4 x 2-1/2 WIRING 7/8” K.O. T’STAT WIRING 7/8” K.O. 23-1/2 2-1/4 8-3/4 1-1/8 30-1/8 LEFT SIDE RIGHT SIDE FRONT 1-1/2 1-1/4 26-3/4 4”...
  • Page 3: Ratings & Physical / Electrical Data - Upflow Models

    278432-YTG-A-0407 RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS Nominal Input Output Cabinet Width AFUE Air Temp. Rise Airflow Models Total Unit Amps °F PS8A12(N,L)040UH11 1200 14-1/2 80.0 25-55 PS8A12(N,L)060UH11 1200 14-1/2 80.0 25-55 PS8A12(N,L)080UH11 1200 14-1/2 80.0 35-65 PS8B16(N,L)080UH11 1600 17-1/2...
  • Page 4 278432-YTG-A-0407 BLOWER PERFORMANCE CFM - UPFLOW (WITHOUT FILTER) - BOTTOM RETURN Bottom Airflow Data (SCFM) Models Speed Ext. Static Pressure (in. H2O) High 1610 1540 1460 1360 1290 1200 1110 1020 Medium High 1430 1390 1330 1250 1190 1110 1030 PS8A12(N,L)040UH11 Medium Low 1200...
  • Page 5 278432-YTG-A-0407 BLOWER PERFORMANCE CFM - UPFLOW (WITHOUT FILTER) - LEFT SIDE RETURN Left Side Airflow Data (SCFM) Models Speed Ext. Static Pressure (in. H2O) High 1810 1730 1660 1570 1480 1390 1300 1200 1090 Medium High 1390 1390 1350 1320 1270 1210 1150...
  • Page 6: Horizontal Sidewall Venting

    278432-YTG-A-0407 HORIZONTAL SIDEWALL VENTING NOTE: The filter pressure drop values in the “Filter Perfor- mance” table shown below are typical values for the type of For applications where vertical venting is not possible, the filter listed and should only be used as a guideline. Actual only approved method of horizontal venting is the use of an pressure drop ratings for each filter type vary between filter auxiliary power vent.
  • Page 7 278432-YTG-A-0407 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. Thermostat Chart Unitary Products Group...
  • Page 8: Applying Filter Pressure Drop To Determine System Airflow

    Pa) to obtain actual airflow @ 0.58 in. w.c. (144 Pa) ESP. 1250 - 56 = 1194 Subject to change without notice. Printed in U.S.A. 278432-YTG-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 246768-YTG-B-0706 Unitary 5005...