High Temperature Protection Of Condenser - Toyotomi DCT 100HSPi Service Manual

Indoor/ outdoor units
Table of Contents

Advertisement

Troubleshooting

9.2.7 High temperature protection of condenser

High temperature protection of condenser
Check the resistance of the temp. sensor
according to Annex 1, is it normal?
Yes
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is
defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
No
Replace the sensor