Superior FVFM27NR Installation And Operating Instructions Manual page 11

Unvented (vent-free) gas log heater
Table of Contents

Advertisement

You must have noncombustible material(s)
above both fireplace openings. Noncombus-
tible materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the fireplace
hood accessory. See Figure 5, page 10 for
minimum clearances.
IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater
with chimney flue damper open. Go to Install-
ing Damper Clamp Accessory for Vented
Operation, page 12.
If Using Mantel
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the fireplace
hood accessory. Even if noncombustible
material is more than 12", you may need the
hood accessory to deflect heat away from
your mantel shelf. See Figure 5, page 10 and
Figures 6 and 7, for minimum clearances.
10"
8"
6"
2
1
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Figure 6 - Minimum Mantel Clearances
Without Using Hood
126848-01A
INSTALLATION
Mantel Shelf
Underside
of Mantel
Shelf
/
"
2
All
minimum
distances
(A)
are in
inches
12"
18" 20"
22"
24"
Distances to
Underside of
Mantel
www.SuperiorFireplaces.US.com
Continued
Minimum
Noncombustible
Material
Figure 7 - Minimum Mantel Clearances
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between fireplace openings and
mantel shelf on each side of the fireplace. If
you do not meet the clearances listed below,
you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fireplace opening, a
hood is not required (see Figure 6).
Determining Minimum Mantel Clearance
When using a Hood
If minimum clearances in Figure 6 are not met,
you must have a hood. When using a hood
there are still certain minimum mantel clear-
ances required. Follow minimum clearances
shown in Figure 7 when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Top of
Fireplace
Walls and mantels above the
Opening
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
Mantel Shelf
12"
10"
8"
6"
2½"
8"
12" 15"
Min.
Hood
Distances to
(GA6050 or
Underside of
GA6053)
Mantel
When Using Hood
Underside
of Mantel
Shelf
18" 20"
Top of
Fireplace
Opening
11