Part 9 - Connect Electrical Power / Initial Startup; Wiring Information - Westinghouse WGRTNG199 Nstallation & Maintenance Manual

Residential tankless water heater
Hide thumbs Also See for WGRTNG199:
Table of Contents

Advertisement

maximum BTU/H rating on the pressure relief valve is equal to or greater than the maximum input BTU/H rating of the combination
water heater.
To avoid water damage or scalding due to relief valve operation:
Discharge line must be connected to relief valve outlet and run to a safe place of disposal. Terminate the discharge line in a
manner that will prevent possibility of severe burns or property damage should the relief valve discharge.
Discharge line must be as short as possible and the same size as the valve discharge connection throughout its entire length.
Discharge line must pitch downward from the valve and terminate at least 6" above the floor drain, making discharge clearly
visible.
Discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375
Do not pipe discharge to any location where freezing could occur.
No shutoff valve may be installed between the relief valve and water heater or in the discharge line. Do not plug or place any
obstruction in the discharge line.
Test the operation of the relief valve after filling and pressurizing the system by lifting the lever. Make sure the valve
discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.
Test relief valve at least once annually to ensure the waterway is clear. If valve does not operate, turn the water heater "off"
and call a plumber immediately.
Take care whenever operating relief valve to avoid scalding injury or property damage.
For water heaters installed with only a pressure relief valve, the separate storage vessel must have a temperature and
pressure relief valve installed. This relief valve shall comply with Relief Valves for Hot Water Supply Systems, ANSI Z21.22
CSA4.4.
FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD RESULT IN FAILURE OF RELIEF VALVE OPERATION,
RESULTING IN POSSIBILITY OF SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.
PART 9 – CONNECT ELECTRICAL POWER / INITIAL STARTUP
Install wiring and electrically ground water heater in accordance with the authority having jurisdiction or, in the absence of such an
authority, follow the National Electrical Code, NFPA 70, and/or CSA C22.1 Electrical Code-Part 1 in Canada. Failure to follow all
applicable local, state, and national regulations, mandates, and building supply codes for guidelines to install the electrical power supply
could result in property damage, serious personal injury, or death.
ELECTRICAL SHOCK HAZARD – To ensure safety, turn off electrical power supply at service entrance panel before making any
electrical connections to avoid possible electric shock hazard. Failure to do so could result in property damage, serious personal injury,
or death.
A. WIRING INFORMATION
1. This water heater must be properly grounded. Ensure the electrical receptacle that the water heater will be plugged into is properly
grounded.
2. Do not attach the ground wire to either the gas or water piping.
Figure 19 – Proper Grounding – Internal Manual Power Switch
26
o
F or greater.
WHL-004 REV. 12.17.14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wgrtlp199Wgrtcng199Wgrtclp199

Table of Contents