Bryant 310A Installation, Start--Up, Operating, And Service And Maintenance page 9

Single-stage deluxe induced-combustion 4-way multipoise gas furnace
Table of Contents

Advertisement

Table 2—Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH)
FURNACE
(1,100 SQ. MM/KW)
INPUT
(BTUH)
Free Area of Open-
ing and Duct
Sq. In. (Sq. mm)
44,000
22 (14194)
66,000
33 (21290)
88,000
44 (28387)
110,000
55 (35484)
132,000
66 (42580)
154,000
77 (49677)
FURNACE
WATER HEATER
110,000
+
30,000
66,000
+
40,000
88,000
+
30,000
Table 3—Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
30
ACH
1,050
0.60
(29.7)
1,260
0.50
(35.6)
1,575
0.40
(44.5)
2,100
0.30
(59.4)
3,150
0.20
(89.1)
(118.9)
6,300
0.10
(178.3)
(237.8)
0.00
NP
NP = Not Permitted
SINGLE DUCT OR OPENING
Round Duct
Free Area of Open-
Dia.
ing and Duct
In. (mm)
Sq. In. (Sq. mm)
6 (152)
14.7 (9484)
7 (178)
22.0 (14193)
8 (203)
29.3 (18903)
9 (229)
36.7 (23677)
10 (254)
44 .0 (28387)
10 (254)
51.3 (33096)
EXAMPLES: Determining Free Area
TOTAL INPUT
=
(140,000 divided by 4,000)
=
(106,000 divided by 3,000)
=
(118,000 divided by 2,000)
40
50
1,400
1,750
1,100
(39.6)
(49.5)
(31.1)
1,680
2,100
1,320
(47.5)
(59.4)
(37.3)
2,100
2,625
1,650
(59.4)
(74.3)
(46.7)
2,800
3,500
2,200
(79.2)
(99.1)
(62.2)
4,200
5,250
3,300
(148.6)
(93.4)
8,400
10,500
6,600
(297.3)
(186.8)
NP
NP
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Round Duct
Dia.
In. (mm)
5 (127)
6 (152)
7 (178)
7 (178)
8 (203)
9 (229)
=
35.0 Sq. In. for each two Vertical Ducts or Openings
=
35.3 Sq. In. for a Single Duct or Opening
=
59.0 Sq. In. for each of two Horizontal Ducts
FAN-ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
44
66
88
3
3
Space Volume Ft
(M
)
1,650
2,200
(46.7)
(62.2)
1,980
2,640
(56.0)
(74.7)
2,475
3,300
(70.0)
(93.4)
3,300
4,400
(93.4)
(124.5)
4,950
6,600
(140.1)
(186.8)
9,900
13,200
(280.3)
(373.7)
NP
NP
NP
9
TWO OPENINGS OR VERTICAL
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of Open-
Round Duct
ing and Duct
Dia.
Sq. In. (Sq. mm)
In. (mm)
11 (7096)
4 (102)
16.5 (10645)
5 (127)
22 (14193)
6 (152)
27.5 (17742)
6 (152)
33 (21290)
7 (178)
38.5 (24839)
8 (203)
110
132
2,750
3,300
3,850
(77.8)
(93.4)
(109.0)
3,300
3,960
4,620
(93.4)
(112.1)
(130.8)
4,125
4,950
5,775
(116.8)
(140.1)
(163.5)
5,500
6,600
7,700
(155.7)
(186.8)
(218.0)
8,250
9,900
11,550
(233.6)
(280.3)
(327.0)
16,500
19,800
23,100
(467.2)
(560.6)
(654.1)
NP
NP
154
NP