Bryant 310A Installation, Start--Up, Operating, And Service And Maintenance page 28

Single-stage deluxe induced-combustion 4-way multipoise gas furnace
Table of Contents

Advertisement

APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance
of the venting system. If the appliances are sized, installed,
adjusted, and operated properly, the venting system and/or the
appliances should not suffer from condensation and corrosion.
The venting system and all appliances shall be installed in
accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates
can be made using approved methods available from Air
Conditioning Contractors of America (Manual J); American
Society of Heating, Refrigerating, and Air- -Conditioning
Engineers; or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace and/or vent to
fail prematurely.
When a metal vent or metal liner is used, the vent must be in
good condition and be installed in accordance with the vent
manufacturer's instructions.
To prevent condensation in the furnace and vent system, the
following precautions must be observed:
1. The return- -air temperature must be at least 60_F (16_C)
db except for brief periods of time during warm- -up from
setback at no lower than 55_F (13_C) db or during initial
start- -up from a standby condition.
2. Adjust the gas input rate per the installation instructions.
Low gas input rate causes low vent gas temperatures, caus-
ing condensation and corrosion in the furnace and/or vent-
ing system. Derating is permitted only for altitudes above
2000 ft. (610 M).
3. Adjust the air temperature rise to the midpoint of the rise
range or slightly above. Low air temperature rise can cause
low vent gas temperature and potential for condensation
problems.
4. Set thermostat heat anticipator or cycle rate to reduce short
cycling.
Exterior Masonry Chimney FAN + NAT
Installations with Type- -B Double- -Wall Vent
Connectors ENFPA & AGA
Table A—Combined Appliance Maximum Input
Rating in Thousands of Btuh per Hour
INTERNAL AREA OF CHIMNEY
VENT HEIGHT
FT. (M)
12
(7741)
6 (1.8)
74
8 (2.4)
80
10 (3.0)
84
15 (4.5)
NR
20 (6.0)
NR
30 (9.1)
NR
Table B—Minimum Allowable Input Rating of
Space- -Heating Appliance in
Thousands of Btuh per Hour
INTERNAL AREA OF CHIMNEY
VENT HEIGHT
FT. (M)
12
(7741)
Local 99% Winter Design Temperature: 17 to 26 degrees F
6
0
8
52
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design Temperature: 5 to 16 degrees F*
6
NR
8
NR
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design Temperature: --- 10 to 4 degrees F*
6
NR
8
NR
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design Temperature: --- 11
Not recommended for any vent configuration.
*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE
Fundamentals Handbook, Climatic Design Information chapter, Table 1A
(United States) and 2A (Canada) or the 2005 ASHRAE Fundamentals
handbook, Climatic Design Information chapter, and the CD ---ROM in-
cluded with the 2005 ASHRAE Fundamentals Handbook.
28
SQ. IN. (SQ. MM)
19
28
38
(12258)
(18064)
(24516)
119
178
257
130
193
279
138
207
299
152
233
334
NR
250
368
NR
NR
404
SQ. IN. (SQ. MM)
19
28
38
(12258)
18064)
(24516)
55
99
141
74
111
154
90
125
169
NR
167
212
NR
212
258
NR
NR
362
78
121
166
94
135
182
111
149
198
NR
193
247
NR
NR
293
NR
NR
377
NR
145
196
NR
159
213
NR
175
231
NR
NR
283
NR
NR
333
NR
NR
NR
_F (16_C)
or
lower

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Series 130/d

Table of Contents