To Remove A Point From A Group Display - Carrier Touch Pilot 33CNTPILOT Installation And Operation Instructions Manual

Table of Contents

Advertisement

TO REMOVE A POINT FROM A GROUP DISPLAY – From
the Point Data Dialog box, press the REMOVE button
and follow the prompts. The display will return to
the Group Display screen from which the point was re-
moved, and the button corresponding to the deleted point
will be blank and disabled.
TO ADD A POINT TO A GROUP DISPLAY – From the
Main Menu, press the one of the table type buttons (Sta-
tus, Setpnt, Service, Maint, or Config) and press the but-
ton corresponding to the table that contains the point you
wish to add to the group (the source point). Press the point
button to show the source point's Point Data dialog box
(Figure 8 and 9). From the Point Data Dialog box, press the
ADD button
. The Display will show the last Group
Display accessed. Use the
tons to access the destination Group Display. Press an ex-
isting point button or a blank button to update the high-
lighted button with the source point's name. Press
to add the highlighted point to the group and return to the
table display.
Figure 8 - Point Data Dialog Box - Dynamic Point
Figure 9 - Point Data Dialog Box - Static Point
Navigation and Operation Pushbuttons – The Touch
Pilot contains the following pushbuttons to allow you to
operate the display and to navigate within and between
screens.
BACK – Returns to the next higher screen in the
hierarchy.
HOME – Displays the Default screen (Default Group
and
navigation but-
Display if one is available, the generic Controller Default
Screen (Figure 7) if the attached device has no Group dis-
plays, or the Main Menu if the display is not attached to a
device).
MAIN MENU – Displays the Main Menu screen. A
description of all Main Menu options can be found in the
Main Menu section of this manual.
PREVIOUS – In a group of sequential screens of the
same type, moves to the next earlier screen in the group.
NEXT– In a group of sequential screens of the same
type, advances to the next screen in the group.
OK – Agrees with, or says "yes" to a prompt and
performs the appropriate processing.
NO – Rejects, or says "no" to a prompt and per-
forms the appropriate processing.
CANCEL – Terminates an ongoing action and re-
turns to the current screen without any other processing.
CLEAR DATA – Blanks the data value in a data
entry dialog box.
RESET DATA – Zeros the data value in a data entry
dialog box.
ADD – Adds a point to a Group Display screen.
REMOVE – Deletes a point from a Group Display
screen.
INC, DEC – Modify the value of a field within
its defined limits.
SCROLL UP, DOWN – Shifts the data on the
screen up or down by one item.
PAGE UP, DOWN – If the current table or list
has more data than will fit on the screen, replace the items
currently on the screen with the previous or next group of
items.
FORCE – Begins the process of forcing or overriding
the value of a point.
AUTO – Begins the process of removing a force
from a point.
MODIFY – Begins the process of modifying a con-
figuration value.
ALARM INDICATOR LIGHT – The Touch Pilot fea-
tures an LED alarm indicator light that is activated when a
new alarm condition has occurred on the Carrier communi-
cating network. The alarm indicator light, located on the
right side of the Display, remains activated until it is manu-
ally reset using the Main Menu's Reset button. When the
Display is in Network mode, the alarm indicator light does
not indicate communication failure with the attached de-
vice.
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents