Check 1 - Proper Chimney Termination; Heck Ny Solid Or Liquid Fuel Appliances Vented Into This Chimney Channel; Heck Himney Rown Ondition - Amana AMH8 Installation Instructions Manual

Gas-fired warm air furnace
Hide thumbs Also See for AMH8:
Table of Contents

Advertisement

Proper Chimney
Termination?
(Check 1)
Yes
Chimney channel
free of solid and
liquid fuel
appliances?
(Check 2)
Yes
Crown in good
condition
(Check 3)
Yes
Cleanout free of
debris?
(Check 4)
Yes
Liner in good
condition?
(Check 5)
Yes
Dilution air
available?
(Check 6)
Yes
Complete the
installation.
(Check 7)
C
1 - P
HECK
ROPER CHIMNEY TERMINATION
A masonry chimney used as a vent for gas fired equipment must
extend at least three feet above the highest point where it passes
through the roof. It must extend at least two feet higher than any
portion of a building within a horizontal distance of 10 feet. In
addition, the chimney must terminate at least 3 feet above any
forced air inlet located within 10 feet. The chimney must extend at
least five feet above the highest connected equipment draft hood
outlet or flue collar.
If the chimney does not meet these termination requirements, but
all other requirements in the checklist can be met, it may be
possible for a mason to extend the chimney. If this will not be
practical, see Fix 1.
Line, terminate with
No
listed vent cap
(Fix 1)
Change venting
No
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
No
and/or Reline
(Fix 4)
Reline
No
(Fix 4)
Reline
No
(Fix 4)
Reline
No
(Fix 4)
.
2' Min.
Ridge
Termination 10 Feet Or Less From Ridge, Wall or Parapet
More Than 10'
NOTE: No height above
parapet required when
distance from walls or
Wall or
parapet is more than 10
Parapet
feet
More than 10'
Ridge
Termination More Than 10 Feet From Ridge, Wall or Parapet
C
2 - A
HECK
NY SOLID OR LIQUID FUEL APPLIANCES VENTED INTO
THIS CHIMNEY CHANNEL
Solid fuel appliances include fireplaces, wood stoves, coal
furnaces, and incinerators.
Liquid fuel appliances include oil furnaces, oil-fired boilers and
oil-fired water heaters.
Appliances which burn propane (sometimes referred to as LP
(liquefied petroleum)) gas are considered gas-fired appliances.
C
3 - C
C
HECK
HIMNEY
ROWN
Damage from condensate usually shows up first in the crown. If
any of the following trouble signs are present, the condition of the
crown is not satisfactory:
12
10' or Less
2' Min.
3' Min.
Wall or
Parapet
Chimney
10' or Less
2' Min.
3' Min.
Chimney
3' Min.
Chimney
Height above any
roof surface within
10 feet horizontally.
10'
2' Min.
3' Min.
Chimney
C
.
ONDITION