Checklist Summary; Roper Chimney Termination - Amana GDH8 Installation Instructions Manual

Gas furnace
Hide thumbs Also See for GDH8:
Table of Contents

Advertisement

P
OSSIBILITY OF PROPERTY DAMAGE
DAMAGING CONDENSATION CAN OCCUR INSIDE MASONRY CHIMNEYS
-
WHEN A SINGLE FAN
ASSISTED
)
FURNACE
IS VENTED WITHOUT ADEQUATE DILUTION AIR
80%
CONNECT AN
FURNACE TO A MASONRY CHIMNEY UNLESS THE
FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED
APPLIANCE OR THE CHIMNEY IS LINED WITH A METAL LINER OR
. A
METAL VENT
LL INSTALLATIONS USING MASONRY CHIMNEYS MUST BE
SIZED IN ACCORDANCE WITH THE APPROPRIATE VENTING TABLES
80%
FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED
,
APPLIANCE
THE POTENTIAL FOR CONDENSATION DAMAGE MAY STILL
EXIST WITH EXTREMELY COLD CONDITIONS
,
EXTERIOR CHIMNEYS
OR ANY COMBINATION OF THESE CONDITIONS
T
HE RISK OF CONDENSATION DAMAGE IS BEST AVOIDED BY USING
MASONRY CHIMNEY AS A PATHWAY FOR PROPERLY SIZED METAL LINER
T
B
.
OR
YPE
METAL VENT
Throat
Damper
Breech
Clean Out
Typical Multiple Flue Clay Tile Chimney
C
S
HECKLIST
UMMARY
This checklist serves as a summary of the items to be checked
before venting an 80+ furnace into a masonry chimney. In addi-
tion, we recommend that a qualified serviceman use this check-
list to perform a yearly inspection of the furnace venting sys-
tem.
This checklist is only a summary. For detailed information on
each of the procedures mentioned, see the paragraph refer-
enced with each item.
This inspection is based upon a draft topical report, "Masonry
Chimney Inspection and Relining", issued by the Gas Research
Institute. While not yet finalized, we believe this report repre-
sents the best information on this subject which is currently
available.
WARNING
,
PERSONAL INJURY OR DEATH
C
I
(80% AFUE
ATEGORY
APPLIANCE
. D
O NOT
,
LONG VENT CONNECTORS
Wash
Roof Line
Clay Tile Size: 8" x 8" x12"
(Each x 24" Length)
Attic Floor
1/2" to 1" Air Space
Second Floor
First Floor
Water Heater
Vent Connector
F.A.F. Vent
Connector
Natural Draft
Fan Assisted
Water Heater
Forced Air
Furnace
Basement Floor
Proper Chimney
Termination?
(Check 1)
Chimney channel
free of solid and
T
B
YPE
liquid fuel
appliances?
(Check 2)
. I
F AN
,
.
Crown in good
condition
(Check 3)
Cleanout free of
debris?
(Check 4)
Liner in good
condition?
(Check 5)
Dilution air
available?
(Check 6)
Complete the
installation.
(Check 7)
C
1 - P
HECK

ROPER CHIMNEY TERMINATION

A masonry chimney used as a vent for gas fired equipment
must extend at least three feet above the highest point where it
passes through the roof. It must extend at least two feet higher
than any portion of a building within a horizontal distance of 10
feet. In addition, the chimney must terminate at least 3 feet
above any forced air inlet located within 10 feet. The chimney
must extend at least five feet above the highest connected equip-
ment draft hood outlet or flue collar.
If the chimney does not meet these termination requirements,
but all other requirements in the checklist can be met, it may
be possible for a mason to extend the chimney. If this will not
be practical, see Fix 1.
13
Change venting
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
and/or Reline
(Fix 4)
Reline
(Fix 4)
Reline
(Fix 4)
Reline
(Fix 4)
.