Fault Codes List - Potterton iHE 100 Installation & Servicing Instructions Manual

Ihe series indirect high efficiency boiler & water heater
Table of Contents

Advertisement

4.5 FAULT CODES LIST

Code Fault Description
10
Outside sensor, error
20
Boiler temperature 1, sensor error
26
Common fl ow temperature, sensor error
28
Flue gas temperature, sensor error
30
Flow temperature 1, sensor error
32
Flow temperature 2, sensor error
40
Return temperature 1, sensor error
50
DHW temperature 1, sensor error
60
Room temperature 1, sensor error
65
Room temperature 2, sensor error
68
Room temperature 3, sensor error
70
Storage tank temperature 1, sensor error
81
LPB Short circuit
83
LPB collision
84
BSB address collision
98
Extension module 1, error
99
Extension module 2, error
100
2 Clock time masters
110
STB lockout
111
Shutdown limit thermostat
119
Shutd water pressure switch
121
Flow temperature heating circuit 1 not reached
122
Flow temperature heating circuit 2 not rached
126
DHW charging temperature not reached
127
DHW legionella temperature not reached
128
Loss of fl ame during operation
130
Flue gas temp too high
133
Safety time exceeded
151
BMU Internal error
152
Parameterization error
153
Unit manually locked
160
Fan speed threshold not reached
171
Alarm contact 1 active
217
Sensor error
218
Pressure supervision
317
Mains frequency outside permissable range
320
DHW Charging temperature, sensor error
323
Water Pressure 3 too low
324
Input BX, same sensors
325
Input BX/extension module, same sensors
326
Input BX/mixing group, same sensors
327
Extension module, same function
iHE
Notes
Check connections and / or replace faulty sensor (B9)
Check connections and / or replace faulty sensor (B2)
Check connections and / or replace faulty sensor (B10)
Check connections and / or replace faulty sensor (B8)
Check connections and / or replace faulty sensor (B1)
Check connections and / or replace faulty sensor (B12)
Check connections and / or replace faulty sensor (B7)
Check connections and / or replace faulty sensor (B3)
Check connections and / or replace faulty sensor (R1)
Check connections and / or replace faulty sensor (R2)
Check connections and / or replace faulty sensor (R3)
Check connections and / or replace faulty sensor (R4)
Check ribbon cable of OCI345 is not shorting on casing
Duplicate LPB address - Check all PCBs function 6600
Room unit incorrectly confi gured - see function 40
Module 1 confi guration error - Check parameters
Module 2 confi guration error - Check parameters
Only PCB no 1 is set as time master - see Function 6640
Check connector X18a and all fl ow & return sensors
Heat exchanger temperatures have been exceeded
Check for condensate or fl ue blockage
Htg Circuit 1, time temp parameter not reached
Htg Circuit 2, time temp parameter not reached
Check operation and heat up times for DHW
Check operation of appliance
Ionisation current lost after successful ignition
Heat Engine is overheating. Check causes of high temperatures
Ignition unsuccessful after 5 attempts
Check polarity is not reversed to the appliance
Incorrect / Confl icting parameters input.
Reset button stuck in
Required fan speed not reached
Condensate or fl ue system blockage
Ionisation current fault.
Check water pressure in heating circuit
Check electrical installaiton
Check connections and / or replace faulty sensor (B36)
Check water pressure in heating circuit
BX sensor duplicated - check parameters
BX extension module sensor duplicated - check parameters
BX Mixing Circuit sensor duplicated - check parameters
Extension Modules duplicated - check parameters
42
Table 3.0
GB/IE