16. setting tHe boiler parameters

The boiler parameters may only be modified by professionally qualified staff proceeding as follows:
a) Press the
, keys on the boiler's front panel together for about 3 s until the parameter H90 appears on
the display;
b) Press the
keys to select the parameter for modification;
c) Press the
and
keys to modify the parameter;
d) Press the
key to exit the programming function.
The following are the parameters generally used:
n° parametro
Description
h90
Setting for domestic hot water reduced temperature (°C)
h91
D.H.W. (Domestic Hot Water) program
(0 = enabled; 1 = disabled)
h505
Maximum temperature (°C) of the central heating circuit HC1 corresponding to:
- the main circuit in systems with just one zone;
- the circuit of the zone where the QAA73 temperature control device is installed in case of
systems with more than one high-temperature zone;
- the high temperature zone circuit in mixed systems and if the SIEMENS AGU2.500
accessory is used.
h507
Maximum temperature (°C) of the central heating circuit HC2 of a system with more than one
zone, corresponding to the circuit of the low-temperature zone if the SIEMENS AGU2.500
accessory is used.
h51
Automatic Summer / Winter switching temperature (°C).
h5
Selection of temperature curve of central heating circuit HC1 (see Graph 1)
h5
Selection of temperature curve of central heating circuit HC2 (see Graph 1)
h5
Maximum speed at maximum output in heating mode (rpm - maximum speed limitation)
h1
Setting value of required speed (rpm) at low-fire
h5-h1
Setting value of required speed (rpm) at high-fire heating / domestic hot water mode
h51-h10
PWM (%) setting: maximum output in heating / domestic hot water mode
h5
Pump post-circulation time in central heating mode (min)
h55
Burner operating pause time between two start-ups (s)
h55
Hydraulic system setting (see instructions provided with the SIEMENS AGU2.500 accessory).
H552 = 50 with AGU2.500
H552 = 80 with RVA 47
h55
Configuration of heating circuits
H553 = 12 with AGU2.500
h15
Programmable function
h
Configuration of system with low loss header P1
H632 = 00001111 with AGU2.500
H632 = 00001000 with storage tank without low loss header
The value of Bit could be 1 or 0.
Press the keys 5 and 6 to select the bit to modify (b0 is the bit on the right, b7 is the last bit
on the left).
To modify the Bit value press on the keys 7 and 8
h1
Fan post-purge interval (s)
h57
Setpoint of autonomous ANTILEGIONELLA function
60...80 °C = setting temperature range
table 4
If the electronic circuit board is replaced, make sure that the parameters set are those specific to the boiler
model, as indicated in the documentation available from the authorised Service Centre.
(*) For these parameters see section 13 (hydraulic system).
InstructIons pErtaInInG to thE InstaLLEr
0 = function inactive

Factory setting
10
1
80
80
20
15
15
Refer to
paragraph 12.1
10
180
2
21
9
00001100
10
0