Section A: Pilot light will not light (new installation).
Is the manual gas shut-off valve,
/
klTurn
the manual gas shut-off valve to
I
located in the supply line to the
I_ NO _
the on position and follow the lighting
I
water heater, in the on position?
1
" l instructions on the front of the water heater.
YES
÷
Have you bled all the air /
.
IWhile repeatedly depressing
the igniter
from the pilot tube and
ImNOml_lbutton,
push in and hold the gas control/
I gas supply line?
l
--Itemperature
knob until the pilot is lit and
.
n
maintains a stable flame (status light will
YES
blink). It may take up to 90 seconds of
pilot operation before status light blinks.
Once status light blinks, release the gas
control/temperature
knob.
!
spark?IS
theNoigniter p roducing a
pYES _
",!,"
Follow the "Testing the Igniter
ISet
to
I
[System
sect on n th s manua.
I
thermostat
desired temperature.
Section B: Pilot light repeatedly goes out.
Check the Base-Ring Filter and
I
Refer to the "Maintenance
of
Flame Arrestor for blockage due i
L.I
your Water Heater" section of this
NO
.
.
.
to lint or dust. Are both the Air
Im
NPl 1 manual for information on cleaning
I Filter and Flame Arrestor clean?
/
Ithe flame arrestor and burner.
YES
Does the flame
arrestor show signs
of discoloration?
Reassemble
the heater, press the thermal
switch, and attempt to return the heater to
service. Does the pilot remain lit?
YES
YES
NO
,[
I Set to desired temperature.
I
,11r-
Does the diagnostic status light on the I
i
Igas control valve/thermostat give
I
La two flash error code?
.o
Refer to the "Replacing the Pilot
I
ego to section C. I
Assemby
nstructons
n the manua.
I
!
I Reassemble
and restore to service. I
Shut-off the gas supply to the water heater at the
I
manual gas shut-off valve, and contact Sears Service
I
at 1-800-MY-HOME
(1-800-469-4663).
Section C: Pilot light wilt not remain lit.
Complete this section after completing Section B.
l Check for insufficient combustion air. I
Y_S
Are the combustion
air supply and ventilation openings
of sufficient size? See "Combustion Air Supply and
IVentilation" section in this manual for requirements.
YES
÷
Does the return air duct for the furnace/
/
1
air handler/air conditioner draw its air from
the same location as the water heater?
NO
See the "Location Requirements" section
and the Combust on A r Supp y sect on.
YES
Contact a Heating and Air
Conditioning
service technician
to relocate the return air duct.
The water heater's pilot can be
extinguished
when the heating
or cooling system is turned on
if the return air duct is in the
same location.
h,.
Correct size of
i NOip,
openings to allow
surf cent a r.
Is there proper
I
I
drafting at the
1
drafthood?
See
I=N01
"Checking the Draft"
l
|
section in this manual.|
i
i
,/---I
Check the vent system
for
restrictions/obstructions
and
check the vent termination
height. Refer to the "Installation
Instructions" section of this
manual for specific requirements.
If you are still having
difficulty
keeping the pilot]
lit,
Contact
Sears
at
1-800-4-MY-HOME
I
(1-800-469-4663)
to request service.
J
NOTE: If you are still experiencing
difficulties
after following the steps in sections A, B, and C,
please contact Sears Service at 1-800-MY-HOME
(1-800-4694663).
I
THERMAL SWITCH LOCATION