Discharge Arrangement - Biasi Unvented Hot Water Cylinders Installation And Maintenance Instructions Manual

Unvented hot water cylinders
Table of Contents

Advertisement

 
DISCHARGE ARRANGEMENT  
Note: It is not acceptable to discharge straight into a soil pipe 
 
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non‐metallic rainwater goods may be damaged by such 
discharges. 
The inlet control group should be positioned so that the discharge from both safety valves can be combined via a 15mm end 
feed Tee, as in the diagram above.  
Connect  the  tundish  and  route  the  discharge  pipe  which  must  be  routed  in  accordance  with  Building  regulation  ‐  Part  G3  of 
schedule 1.  
When operating normally water will not be discharged. Water discharge from the two safety valves will only occur under fault 
conditions.  
The tundish should be vertical, located in the same space as the unvented hot water storage system and be fitted as close as 
possible, within 500mm of the safety device e.g. the temperature relief valve.  
The position of the tundish must be that when installed it is visible to the occupants of the premises. 
When  positioning  the  tundish,  the  drain  valves  and  motorised  valve  ensure  that  these  items  are  positioned  away  from  any 
electrical devices. 
 
The  discharge  pipe  (D2)  coming  from  the  tundish  should  terminate  in  a  safe  place  where  there  is  no  risk  to  persons  in  the 
vicinity of the discharge, be of metal and: 
A) Be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic 
resistance  exceeds  that  of  a  straight  pipe  9m  long,  i.e.  discharge  pipes  between  9m  and  18m  equivalent  resistance 
length should be at least two sizes larger than the nominal outlet size of the safety device, between 18 and 27m at 
least 3 sizes larger, and so on. Bends must be taken into account in calculating the flow resistance. Refer to diagram 1, 
Table  1  and  the  worked  example.  An  alternative  approach  for  sizing  discharge  pipes  would  be  to  follow  BS6700 
Specification  for  design,  installation,  testing  and  maintenance  of  services  supplying  water  for  domestic  use  within 
buildings and their curtilages. 
B) Have a vertical section of pipe at least 300mm long, below the tundish before any elbows or bends in the pipework. 
C) Be installed with a continuous fall. 
D) It is preferable for the discharge to be visible at both the tundish and the final point of discharge. Where this is not 
possible or practically difficult, there should be clear visibility at one or other of these locations.  
 
 
Examples of acceptable discharge arrangements are: 
1. Ideally below the fixed grating and above the water seal in a trapped gulley.  
2.  Downward  discharges  at  a  low  level;  i.e.  up  to  100mm  above  external  surfaces  such  as  car  parks,  hard  standings,  grassed  areas  etc.  are 
acceptable providing that where children play  or otherwise come into contact with discharges, a wire cage or similar guard is positioned to 
prevent contact whilst maintaining visibility. 
3. Discharges at a high level; e.g. in to metal hopper and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or 
 
unvented hot water cylinders  
installation and maintenance instructions
Page 5 / 20
 

Advertisement

Table of Contents
loading

Table of Contents