Siting The Unit; Schematic Diagram; Water Supply - Biasi Unvented Hot Water Cylinders Installation And Maintenance Instructions Manual

Unvented hot water cylinders
Table of Contents

Advertisement

 
SITING THE UNIT  
This unit can supply outlets above it or at some distance from it but any outlets above the unit will reduce the available outlet 
pressure by 0.1 bar for every 1m of height difference. The maximum length of the "dead leg" should be as stated in the Water 
Supply (Water Fittings) Regulations 1999 G18.7, in particular to the area of most frequent use.  
 
Particular  attention  is  needed  if  sitting  in  a  garage  or  outbuilding  as  the  unit  should  be  protected  from  frost.  All  exposed 
pipework  must  be  insulated.  The  unit  must  be  installed  UPRIGHT  on  a  flat  base  capable  of  supporting  its  weight  when  full 
(please see the technical specification section for weights). The minimum recommended cupboard size is 650mm square.  
 
Sufficient  access  to  allow  maintenance  of  the  valves  should  be  considered.  In  addition  the  immersion  heaters  are  400mm  in 
length and this distance should be considered to allow withdrawal for servicing if required. The discharge pipework from the 
safety valves should fall continuously and terminate safely. 
SCHEMATIC DIAGRAM  
SECONDARY
FLOW
SECONDARY RETURN CIRCUIT
(200, 250 & 300 LITER SIZES)
1
2
3
PRIMARY
FLOW
DUAL
STAT
PRIMARY
RETURN
9
 
WATER SUPPLY  
The  performance  of  any  unvented  system  is  only  as  good  as  the  mains  water  supply  available.  To  this  effect  the  maximum 
possible  water  demand  should  be  assessed,  with  the  knowledge  that  the  mains  supplies  both  hot  and  cold  services 
simultaneously. 
 
The water heater itself operates at a pressure of 3 bar, controlled by the inlet control set, and is capable of delivering over 50 
litres per minute. The high quality inlet control set has been designed to make the most of the flow rates available.  
 
The water supply should be checked to ensure it can meet these requirements. If necessary, consult the local water authority 
regarding the likely pressure and flow rate availability.  
Consideration  should  be  given  to  upgrading  existing  ½"  (15mm)  cold  mains  pipework  to  a  larger  size  if  the  recommended 
minimum pressure/flow rate is not being achieved.  
 
Note: A high static (no flow) mains pressure is no guarantee of good flow availability. In a domestic installation 1.5 bar and 25 
l/min. should be regarded as the minimum. The maximum mains pressure that the inlet control set can cope with is 10 bar.
 
4
5
COLD FEED
unvented hot water cylinders  
installation and maintenance instructions
6
FLEXIBLE HOSE
COLD
MAIN
2
7
8
BALANCED COLD
CONNECTION
 
Legend: 
1. Bronze Pump 
2. Non Return Valve 
3. Two Port Valve 
4. Temperature & Pressure Relief Valve 
5. Expansion Relief Valve 
6. Expansion Vessel with wall bracket 
7. Pressure Reducing Valve 
8. Isolating Valve 
9. Drain Valve (not supplied) 
Note: 
The pressure reducing valve, non‐return 
valve and expansion relief valve are 
combined together in the inlet control et. 
On 125‐170L sizes there is no dedicated 
secondary return boss and the secondary 
return circuit should be tee'd into the 
cool feed pipe just above the drain elbow.
Page 3 / 20

Advertisement

Table of Contents
loading

Table of Contents