Connection Of The Pipes-Outdoor - LG TMNC092DYAA Service Manual

Multi type air conditioner
Table of Contents

Advertisement

• Bad case
• Following bending type from right to left could cause
problem of pipe damage.
46 Mutli Air Conditioner
Flaring work and connection of piping

Connection of the pipes-Outdoor

Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure
the direction for tightening follows the arrow on the wrench.
Outside diameter
mm
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Ø19.05
Outdoor unit
Torque
kg . m
inch
1/4
1.8
3/8
4.2
1/2
5.5
5/8
6.6
3/4
6.6
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench

Advertisement

Table of Contents
loading

Table of Contents