Connection Of The Pipes-Outdoor - LG TS-C096EMA0 Service Manual

Room air conditioner
Table of Contents

Advertisement

Flaring work and connection of piping
• Bad case
• Following bending type from right to left could cause
problem of pipe damage.
24 Room Air Conditioner

Connection of the pipes-Outdoor

Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure
the direction for tightening follows the arrow on the wrench.
Outside diameter
mm
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Ø19.05
Outdoor unit
Torque
kg . m
inch
1/4
1.8
3/8
4.2
1/2
5.5
5/8
6.6
3/4
6.6
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench