Blocking Errors - Worcester 27i System Compact Installation, Commissioning And Servicing Instructions

Greenstar i system compact series wall hung rsf gas fired condensing system boiler
Table of Contents

Advertisement

Cause
Fault codes
codes
Description
F0
237
Internal error
238
Gas valve error
239
242 - 256
258
259
Internal error
262
263
267
272
279
290
278
Sensor test failed
280
Recycle time error
338
Too many short burner starts without
confirmation
F7
228
Flame error
328
Internal error
FA
306
False flame error
FD
231
Mains power error
FA
364
Gas valve EV2 leak test failed
Fb
365
Gas valve EV1 leak test failed
Table 20 Locking fault and cause code listing

BLOCKING ERRORS

Fault
Cause
code
code
Description
A1
281
Pump stuck or running in air
C1
264
Airflow stopped during operation
C4
273
Airflow present during last 24 hours
D1
240
Return sensor short circuit
241
Return sensor disconnected
D4
271
Temperature difference between flow and
safety sensors exceeds limit
E9
224
MAX thermostat activated
276
Flow temperature exceeds 95°C
277
Safety temperature exceeds 95°C
285
Return temperature exceeds 95°C
EA
227
No ionisation detected after ignition
EF
349
Central heating, boil detect.
Large delta T despite minimum burner.
No
212
Safety or flow temperature rises too fast
code
213
Temperature difference between supply and
return exceeding limit
260
No temperature rise after burner starts
380
Inlet DHW temperature higher than the DHW
outlet temperature.
Table 21 Blocking codes
Greenstar i System Compact - 6 720 807 726 (2013/05)
Reset type
Possible cause
Call Worcester, Bosch Group Technical helpline 0844 892 3366
Reset button Leaking gas valve
Call Worcester, Bosch Group
Technical helpline 0844 892 3366
Reset button On power up all safety sensors are checked.
Check has failed.
Reset button After the burner has stopped, the recycle mode purges gas from the
heat exchanger before attempting to burn again. The software has
3.1 seconds to intervene before the boiler goes into this fault
condition.
Reset button There is an error where the pump is not detecting water.
Reset button False flame. Flame detected before burner start.
Replace control board
Reset button Flame detected after burner stop
Reset button Electrical power interruption.
Reset button Gas valve leak.
Reset button Gas valve leak.
Possible cause
Little or no water in the system.
Fan has stopped.
Fan has been running continuously during the past 24 hours.
Wet sensor.
Blocking for 300 seconds before going to Locking error ( table 20).
Blocking for 300 seconds before going to Locking error ( table 20).
The temperature of the primary flow and the safety sensor on the WB7 should
be within 15°C of each other.
Flue gas thermostat overheat.
Primary overheat - boiler waits for temperature to reduce; if not it becomes a
Locking error.
Main heat exchanger safety sensor overheat - boiler will wait for the
temperature to reduce; if not it becomes a Locking error 219.
The boiler will stop the burn and wait to see if it cools down. If after 2 seconds
there is an increase in temperature the boiler will go to Locking error 286.
No flame is detected. The boiler will block during 4 attempts before going to
Locking fault.
The boiler is operating at minimum burner load and there is a greater than
18°C Flow & Return temperature difference.
Air lock or reduced water content.
Air lock or reduced water content.
Sensor disconnected or no water content.
The output is blocked until the inlet temperature drops below the output
temperature.
FAULT FINDING AND DIAGNOSIS