Installation Of Fireplace; Install The Dual Cooling Air Kit - Heat & Glo Montana-36 Owner's Manual

Woodburning fireplace
Hide thumbs Also See for Montana-36:
Table of Contents

Advertisement

4 4

Installation of Fireplace

CAUTION
Sharp Edges
Wear protective gloves and safety glasses
during installation.
A. Install the Dual Cooling Air Kit
The cooling air kit is supplied as a standard feature with this
fi replace and is required for safe operation. Installation must
be done at the time of initial construction. The cooling air in-
let tubes must be a minimum of 72 in. (1829 mm) above the
base of the fi replace to prevent potential blockage by snow
or yard debris. See Figure 4.1.
To install the air kit collar, slide one of the tabs down into the
seam. See Figure 4.2. Secure the collar tabs to the fi replace
with screws placed into the holes provided. See Figure 4.3.
Repeat for other side.
Note: The cooling air kit must terminate at least 6 ft. (1.83 m)
above ground level.
72 in./183 cm
min.
Figure 4.1
Cooling Air Location
Heat & Glo LifeStyles Collection • Montana US-CAN • 4039-156 Rev C • 11/07
TR11/TR444
Termination
Cap
11-10 in./279-254 mm
adapter not shown
WARNING
Fire Risk
Asphyxiation Risk
Do not draw outside combustion air from:
Wall, fl oor or ceiling cavity.
Enclosed space such as an attic or
garage.
Close proximity to exhaust vents or
chimneys.
Fumes or odor may result.
Figure 4.2
Slide the Tabs
Figure 4.3
Secure the Tabs
13