Troubleshooting; Furnace Components - Heat Controller 80+ AFUE Installation Instructions Manual

Single stage high efficiency gas furnaces
Table of Contents

Advertisement

TROUBLESHOOTING

If the furnace fails to operate check the following:
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the furnace disconnect closed?
• Has the circuit breaker tripped or the control board fuse
burned open?
• Is the gas turned on?
• Are any manual reset switches open?
• Is the filter dirty or plugged?
• Is the flame sensor coated? (Remove and clean with
steel wool).
• Are all the LED's on the furnace control board constantly
ON? If not, refer to Table 11 or the wiring diagram (Figure
19, page 30) to determine fault condition.
IMPORTANT NOTE: The furnace will lock out after 5
failed attempts for ignition and will try again every
hour if the call for heat remains.
• If the inducer blower is operating and items above have
been verified, check the blower limit switch and reset
if necessary. See Figure 20 (page 35) for component
location.
The descriptions below are various functional components that affect the operation and shutting down of this furnace.
Some of these components and their locations are shown in Figure 20 (page 35). If any component of the furnace must
be replaced, use only factory authorized replacement parts specified in the Replacement Parts List provided online.
Blower Limit Switch - Prevents operation when blower is not operational.
Flame Sensor - Verifies when a flame has carried over from the igniter to the opposite end burner. If no flame is
detected, the furnace will shut down within 4 seconds.
Flame Roll-Out Switch - Verifies that the burner flames are drawn into the heat exchanger tubes. If the burner
flames are not properly drawn into the heat exchanger, the flame roll-out switch will close the gas valve and initiate
the shutdown cycle.
Gas Valve - Controls the flow of gas to the burners. When the gas valve is energized it automatically opens and
regulates the gas pressure in the manifold.
Inducer Assembly - Vents products of combustion to the outside.
Pressure Switch - Verifies that the inducer is drawing the combustion gases through the heat exchanger. The
pressure switch prevents furnace operation with excessive flue blockage or improper inducer operation.
Supply Air Limit Switch - Prevents the air temperature leaving the furnace from exceeding the maximum allowable
outlet air temperature.
34
• If the furnace operates when the blower limit switch is
reset, contact a qualified service technician to identify
and repair the problem.
• If the furnace still doesn't operate, check the flame
roll-out switch and reset if necessary. See Figure 20
for component location.
• If the furnace operates when the flame rollout switch is
reset, contact a qualified service technician to identify
and repair the problem.
Diagnostic Description
Control Fault (No Power)
L1/Neutral Polarity Fault
1 Hour Lockout
Normal Operation
Pressure Switch Closed Fault
Pressure Switch Open Fault
Open Limit Switch Fault
Motor Fault
Diagnostic Description
Low Flame Sensor Signal
Flame Present
Table 11. Control Board Fault Conditions

FURNACE COMpONENTS

Green LED
Red LED
Off
Off
Flash
Flash
Alternating Flash
On
On
On
Flash
Flash
On
Flash
Off
On
Off
Yellow LED
Continuous Flash
On