INSERT PELLET STOVE INSTALLATION ‐ continued 
Minimum Clearance to Combustibles and Floor Protection 
 
 
A: Side wall: 16" to side of appliance 
B: Top Trim: 5" above top of appliance 
C: Side trim: 10.5" to side of appliance 
D: Mantle: 10" above top of appliance                  
Floor Protection 
When in MASONRY fireplaces, use ½ inch thick non‐combustible material.  
When in Factory‐built fireplaces, use a 1 inch, non‐combustible surface with a k factor of 0.84. For multiple layers, 
add R‐values of each layer to determine the overall R‐value. The R value for the required board is 1.2. 
 
Convert specification to R‐value: 
k‐factor is given with a required thickness (T) in inches: R=1/k x T.  The C‐factor is given: R=1/C 
Example: 
If the floor protector is 4" brick with a C‐factor of 1.25 over 1/8" mineral board with a "k" factor of 0.29 the total R‐
value of the system is: 
4" brick C=1.25, R=1/1.25=0.8 
1/8" mineral board K=0.29, R=1/0.29 x 0.125=0.431 
Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231 
Total R is greater than 1.2, the system is acceptable.
 
 
 
 
 
 
 
 
 
 
 
6
 
 
Figure 20
27 
 
 