INSTALLING YOUR ROOM HEATER ‐ continued
 
1. Locate your Pellet Stove Room Heater in a location which meets the requirements of this manual, but 
in an area where it does not interfere with the house framing, wiring, etc. 
Install a non‐combustible hearth pad underneath the pellet stove. This pad should extend at least 6" 
2.
(152mm) in front of the unit.
3. Place your Pellet Stove Room Heater on the hearth pad and locate the unit in manner that will leave 
the exhaust vent with a minimum of 3" (75mm) clearance to any combustible wall. 
4. When installing the air intake, locate the center of the combustion air intake pipe at the back of your 
unit. Line up the center with the same spot on your exterior wall and cut a 2‐1/2" (64mm) diameter 
hole through the wall. 
5. Secure  all  vent  joint  connections  with  3  screws.  Seal  the  exhaust  vent  joint  connections  with  high 
temperature silicone sealant. 
6. Install the combustion air intake pipe. 
7. Install a tee, with a cleanout, on the exhaust pipe found at the rear of your unit. 
8. Install approved vent upward through the ceiling. When you pass through the combustible framing 
ensure  that  the  appropriate  ceiling  firestop  is  used.  You  must  maintain  a  minimum  3"  (75mm) 
clearance to combustibles and keep any insulation away from the exhaust vent. 
9. Extend the exhaust vent through the roof flashing and ensure that the vertical cap is approximately 
36" (900mm) above the roof. 
FREESTANDING INTERIOR VERTICAL INSTALLATION 
 
 
 
17 
 