INSTALLING YOUR ROOM HEATER ‐ continued 
 
 
1. Locate your pellet stove in a location which meets the requirements of this manual, but in an area 
where it does not interfere with the house framing, wiring, etc. 
2. Install a non‐combustible hearth pad underneath the pellet stove. This pad should extend at least 6" 
(152mm) in front of the unit. 
3. Place the pellet stove approximately 15" (381mm) away from the interior wall. 
4. Locate the center of the exhaust pipe of your unit. This point should then be extended to the interior 
wall of your house. Once you have located the center point, on the interior wall, cut a 7" (175mm) 
diameter hole through the wall. 
5. The next step is to install the wall thimble, refer to the instructions which come with the wall thimble 
for this step.  
6. Install  the  appropriate  length  of  exhaust  vent  pipe  into  the  wall  thimble.  See  step  11  when 
determining the correct length of exhaust vent to use.  
7. Outside Fresh Air is Mandatory when installing this pellet stove room heater in airtight homes and 
mobile homes.  Be sure that the outside air vent has an approved cap on it to prevent rodents from 
entering. Be sure to install in location that won't become blocked with snow, etc. 
8. The  air  intake  pipe  is  equipped  with  a  butterfly  valve  that  is  preset  to  maximum  air  intake.    For 
optimum  operating  efficiency  you  may  calibrate  the  butterfly  valve  to  provide  less  intake  air.  (See 
Figure  7)    Caution:  Too  much  restriction  on  the  intake  air  will  cause  dirtier  burn,  therefore,  will 
require more frequent cleaning. 
 
 
9. Connect the exhaust vent pipe to the exhaust outlet of your pellet stove. 
10. Secure  all  vent  joint  connections  with  3  screws.  Seal  the  exhaust  vent  joint  connections  with  high 
temperature silicone sealant. 
11. Push  the  unit  straight  back  to  the  interior  wall,  being  sure to  maintain  the  minimum  clearances  to 
combustibles  6"  (152mm)  to  the  back  of  the  unit.    Seal  the  annular  space  of  the  wall  thimble  and 
around the vent pipe with high temperature silicone sealant. 
12. The exhaust vent pipe must extend at least 12" (300mm) out past the exterior wall. Seal the annular 
space of the wall thimble and around the vent pipe with high temperature silicone sealant. 
13. Install  an  approved  horizontal  termination  cap  or  if  necessary  install  a  90°  elbow  and  appropriate 
length of vertical venting. An approved vertical vent cap is recommended.  
 
HORIZONTAL EXHAUST VENT INSTALLATION 
 
 
 
 
15 