Slim Duct Type
Installation under high-humidity atmosphere
In some cases including the rainy season, especially inside of the ceiling may become high-humidity
atmosphere (dew-point temperature: 23°C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the fresh air
• In the above cases, additionally attach the heat insulator to all positions of the air conditioner, which
come to contact with the high-humidity atmosphere. In this case, arrange the side plate (Check port)
so that it is easily removed.
• Apply also a sufficient heat insulation to the duct and connecting part of the duct.
[Reference] Dewing test conditions

Installation space

Reserve space required for maintenance the indoor unit and service work.
Ceiling
5-EN
Indoor side:
27°C dry bulb temperature
24°C wet bulb temperature
Air volume:
Low air volume, operation time 4 hours
100 or more
<Under air Inlet>
5 or more
210
Air outlet
50 or more
2500 or more
Floor surface
Air outlet
250
or more
235
or more
Ceiling
– 5 –
Installation Manual
5 or more
235 or more
210
<Back air Inlet>
5 or more
Air outlet
210
300 or more
2500 or more
Floor surface
(Unit:mm)
235
or more