System Z10 Ec Physical Characteristics - IBM System z10 EC Reference Manual

Ibm system z10 enterprise class
Hide thumbs Also See for System z10 EC:
Table of Contents

Advertisement

System z10 EC Physical Characteristics

System z10 EC Environmentals
Model
1 I/O Cage
E12
9.70 kW
E26
13.77 kW
E40
16.92 kW
E56
19.55 kW
E64
19.55 kW
Model
1 I/O Cage
E12
33.1 kBTU/hr 46.0 kBTU/hr 46.0 kBTU/hr*
E26
47.7 kBTU/hr 61.0 kBTU/hr 73.7 kBTU/hr
E40
58.8 kBTU/hr 72.0 kBTU/hr 84.9 kBTU/hr
E56
67.9 kBTU/hr 81.2 kBTU/hr 93.8 kBTU/hr
E64
67.9 kBTU/hr 81.2 kBTU/hr 93.8 kBTU/hr
Note: Model E12 has sufficient Host Channel Adaptor capacity for 58 I/O
cards only
2 I/O Cage
3 I/O Cage
13.26 kW
13.50 kW
21.17 kW
17.51 kW
20.66 kW
24.40 kW
23.29 kW
27.00 kW
23.29 kW
27.50 kW
2 I/O Cage
3 I/O Cage
46
z10 EC and z9 EC Dimension Comparison
System
z10 EC
# of Frames
2 Frames
IBF contained
w/in 2 frames
Height (w/ covers)
201.5 cm / 79.3 in
Width (w/ covers)
156.8 cm / 61.7 in
Depth (w/ covers)
180.3 cm / 71.0 in
Height Reduction
180.9 cm / 72.1 in
Width Reduction
None
Machine Area
2.83 sq. meters /
30.44 sq. feet
Service Clearance
5.57 sq. meters /
60.00 sq. feet
(IBF contained
w/in the frame)
System
z9 EC
2 Frames
IBF contained
w/in 2 frames
194.1 cm / 76.4 in
156.8 cm / 61.7 in
157.7 cm / 62.1 in
178.5 cm / 70.3 in
None
2.49 sq. meters /
26.78 sq. feet
5.45 sq. meters /
58.69 sq. feet
(IBF contained
w/in the frame)