LENNOX HEARTH PRODUCTS • MERIT PLUS
HORIZONTAL VENT FIGURES/TABLES (continued)
H 1
Wall Firestop/
Spacer
SV4.5HF**
V
Square termination (SV4.5HT-2) shown.
Figure 38: Rear Vent—TWO 90-DEGREE ELBOWS
H 1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range
of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical
rise (See Page 13).
Figure 39: Top Vent—TWO 90-DEGREE ELBOWS
22
DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
®
H
Ceiling
Firestop/Spacer
SV4.5VF*
*When using Secure Flex , use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Wall Firestop/Spacer
SV4.5HF**
Wall Firestop/Spacer
SV4.5HF**
Ceiling Firestop/Spacer
SV4.5VF*
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H
+H
feet
5
10
15
20
Example: If 20 feet of (H) horizontal vent run is needed, then 4
feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
®
See Table 9 on Page 21 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with
more than 8 ft of vertical rise (See Page 13).
H
V
TABLE H
Maximum
H Maximum
1
(meters)
(meters)
feet
(1.524)
2
(0.610)
(3.048)
4
(1.219)
(4.572)
6
(1.829)
(6.096)
8
(2.438)
V + H + H 1 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H 1 = 20 feet (6.096 meters) Max.
TABLE J
H
Maximum
+ H
1
feet
(meters)
(0.914)
3
(1.524)
5
(3.048)
10
(4.572)
15
20
(6.096)
H
V +
+ H
= 40 feet (12.2 m) Max.
1
H
+ H
= 20 ft. (6.096 m) Max.
1
Example: If 20 feet of (H) horizontal vent run is
needed, then 4 feet minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every
1 foot of (V) vertical, you are allowed 5 feet of (H)
horizontal run, up to a maximum horizontal run of
20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 36.
V Minimum
(meters)
feet
1
(0.305)
2
(0.610)
3
(0.914)
4
(1.219)
V Minimum
(meters)
feet
Elbow Only
1
(0.305)
2
(0.610)
3
(0.914)
4
(1.219)