B. Using Offsets/Returns
Use an offset/return to bypass overhead obstructions.
An offset and return can be used as a single entity or separated by chimney section(s).
WARNING! Risk of Fire! DO NOT use offset/returns greater than 30°. Chimney draft will be restricted and could cause
overheating and fire.
Measure the shift needed to avoid the overhead obstruction. Refer to dimension A in Figure 8.3.
Find the appropriate A dimension listed in Table 8.2.
The B dimension coinciding with the A dimension measurement in Table 8.2 represents the required vertical clearance
needed to complete the offset/return.
Read across the chart to find the number of chimney sections/model numbers needed between the offset and return.
A
B
1-1/4 in. (32 mm)
OVERLAP
Figure 8.3
Chimney Offset/Return
Table 8.2
15-degree
A
B
Offset
Height
in.
mm
in.
1-5/8
4
13-3/8
2-7/8
73
17-3/4
4-1/8
02
22-3/8
4-1/2
4
23-5/8
5-3/4
46
28-1/4
6
52
29-3/8
7-1/4
84
34
7-3/4
97
36-1/8
8-3/4
222
39-3/4
10-3/8
264
45-5/8
10-5/8
270
46-3/4
11-7/8
302
51-3/8
13-1/2
243
57-1/4
13-3/4
349
58-3/8
5
38
63
16-1/2
49
68-3/4
8
457
74-5/8
19-5/8
498
80-3/8
20-5/8
524
84-1/8
22-3/4
578
91-7/8
24
60
96-1/2
25-7/8
657
103-1/2
Proper assembly of air-cooled chimney parts result in an overlap at chimney joints of 1-1/4 in. (32 mm). Effective length is built
into this chart.
26
mm
SL306 SL312 SL318 SL324 SL336 SL348
340
-
-
-
45

-
-
568
2
-
-
600
-

-
78


-
746
-
-

864
-
2
-
98
-
-
-
00

-
-
59
-
-
2
87
-
-
-
305

-
-
454
-
-
-
483
-
-
-
600

-
-
746
-

-
895
-
-

2042
-
-
-
237

-
-
2334
-
-
-
245

-
-
2629
-
-
-
Heatilator • A36R & A42R • 28376 • Rev AJ • 08/09
Example:
Your "A" dimension from Figure 8.3 is 4 /2 in. (368
mm). Using Table 8.2 the dimension closest to, but
not less than 4 /2 in. (368 mm) is 4 /2 in. (368
mm) using a 30° offset/return.
You determine from the table that you need 34 /8 in.
(867 mm) (Dimension "B") between the offset and
return.
The chimney component that best fits your applica-
tion is one SL324.
-
-
-
3-5/8
-
-
-
5-1/2
-
-
-
7-1/4
-
-
-
8-1/2
-
-
-
10-1/4
-
-
-
11-1/2
-
-
-
13-1/4

-
-
14-1/2

-
-
16-1/4
-
-
-
19-1/4
-

-
20-1/2
-

-
22-1/4
2
-
-
25-1/4
-
-

26-1/2
-
-

28-1/4
-
-

31-1/4
-
-

34-1/4

-

37-1/4

-

39-1/8
-


43-1/4
-


45-1/8
-
-
2
49-1/4
30-degree
A
B
Offset
Height
in.
mm
in.
mm
92
15-1/2
394
40
18-5/8
473
84
21-3/4
552
26
23-3/4
603
260
27
686
292
29
737
337
32-1/8
86
368
34-1/8
867
43
37-3/8
949
489
42-1/2
080
52
44-5/8
33
565
47-3/4
23
64
52-7/8
343
673
55
397
78
58-1/8
476
794
63-1/4
607
870
68-1/2
740
946
73-3/4
873
994
76-7/8
953
099
84-1/8
237
46
87-1/4
226
25
94-1/2
2400

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A36rhA42rA42rh

Table of Contents