Input Current Control - Daikin BA-Series Service Manual

Inverter pair floor / ceiling suspended dual type ba-series
Table of Contents

Advertisement

Control Specification
3.5

Input Current Control

Outline
The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of frequency and takes
priority over the lower limit control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
Dropping zone
Keep zone
Reset zone
Limitation of current dropping and stop value according to the outdoor temperature
45
(A)
A
B
C
Input current
After 2.5 seconds in this zone, the compressor is stopped.
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep
zone.
The present maximum frequency goes on.
Limit of the frequency is canceled.
RK(X)S25E2V1B
Cooling
Heating
A
(A)
9.25
B
(A)
6.0
7.5
C
(A)
5.25
6.75
RXS25K3V1B
Cooling
Heating
A
(A)
9.25
B
(A)
7.5
C
(A)
6.75
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
Compressor Stop
RK(X)S25G2V1B9
RK(X)S25G2V1B
Cooling
Heating
Cooling
9.25
6.5
7.5
6.25
5.75
6.75
5.5
RK(X)S35G2V1B9
RK(X)S35E2V1B
RK(X)S35G2V1B
Cooling
Heating
Cooling
9.25
7.25
8.25
6.5
7.5
SiBE05-722ED
Stop Zone
Dropping Zone
Keep Zone
Reset Zone
(R14643)
RXS25J2V1B
Heating
9.25
7.5
6.75
RXS35J2V1B
RXS35K2V1B
RXS35L2V1B
Heating
9.25
8.25
7.5
Function and Control