lations.
Where a room-sealed appliance is in-
stalled in a room containing a bath or
shower, any electrical switch or appli-
ance control, utilising mains electricity
should be so situated that it cannot be
touched by a person using the bath or
shower.
The location must permit the provision of an
adequate flue and termination.
For unusual locations special procedures
may be necessary and BS 6798 gives de-
tailed guidance on this aspect.
A compartment used to enclose the appli-
ance must be designed specifically for this
purpose. This appliance is not suitable for
external installation.
5.3

Flue system

The provision for satisfactory flue termina-
tion must be made as described in BS 5440
part 1. For Ireland (IE), refer to I.S.813.2002.
The appliance must be installed so that the
flue terminal is exposed to external air.
It must not be installed so that the terminal
discharges into an other room or space as
an outhouse or lean-to. It is important that
the position of the terminal allows a free
passage of air across at all times.
The terminal should be located with due
regard for the damage or discoloration that
might occur to building products in the vicin-
ity.
In cold and/or humid weather water vapour
may condense on leaving the flue terminal;
the effect of such "steaming" must be con-
sidered.
Pluming may easily occur at the terminal.
Where possible, terminal position which
- 32 -
- 32 -
GENERAl REQUIREMENTS
could cause a nuisance should be avoided.
The minimum acceptable spacing from
the terminal to obstructions and ventilation
openings are specified in Fig. 5.1.
BC
G
E
L
JK
I
Fig. 5.1
Terminal position
A Directly below the window or
other opening
b Below gutters, soil pipes or
drain pipes
C Below eaves
D Below balconies*
E Below car port roof
F From vertical drain pipes and
soil pipes
G From internal corners**
H From external corners
I
Above ground or balcony lev-
el***
J From a next door boundary
K From a terminal facing a termi-
nal
l From an opening in the car port
(e.g. door, window) into dwell-
ing
M Vertically from a terminal in the
same wall
N Horizontally from a terminal in
the same wall
O
H
P
I
F
A
D
Q
I
M
N
I
I
mm
300
75
200
600
NO
150
450
300
300
2500
2500
NO
1500
300