Mitsubishi Electric PLA-A·BA4 Technical Data Manual page 5

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for PLA-A·BA4:
Table of Contents

Advertisement

2-2. INVERTER WALL-MOUNTED TYPE
Indoor unit
Model name
Outdoor unit
Cooling
Max. Capacity
Rated Capacity
Min. Capacity
Total Input
EER
SEER
Moisture Removal
*1 SHF
Heating
Max. Capacity
Rated Capacity
Min. Capacity
Total Input
COP
*1 HSPF (IV/V)
Heating
Rated Capacity
at low ambient
Total Input
*2 COP
Phase, Cycle, Voltage
Power supply
Breaker size
Indoor - Outdoor S1-S2
Voltage
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
Indoor unit
MOCP
Fan Motor
Fan Motor Output
Air flow
(Lo-Mid-Hi) WET
Air flow
(Lo-Mid-Hi) WET
External pressure
Sound level
(Lo-Mid-Hi)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Field drain pipe size I.D.
Remote Controller
Outdoor unit
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant
Type
Charge
Oil
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
Height difference
Length
Refrigerant Piping
Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F)
Operating range
Maximum
Cooling
Minimum
Maximum
Heating
Minimum
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5°C(23°F)DB.)
PUY-A12NHA4
PUY-A12NHA4-BS
Btu/h
Btu/h
Btu/h
W
Btu/h/W
Btu/h/W
Pints/h
Btu/h
Btu/h
Btu/h
W
W/W
Btu/h/W
Btu/h
W
W/W
A
A
A
F.L.A.
W
DRY
CMM
CMM
DRY
CFM
CFM
Pa
dB(A)
W : mm [inch]
D : mm [inch]
H : mm [inch]
kg
lbs
mm [inch]
A
A
F.L.A.
W
R.L.A
L.R.A.
CMM [CFM]
dB(A)
dB(A)
W : mm [inch]
D : mm [inch]
H : mm [inch]
kg [lbs]
kg [lbs, oz]
L [oz]
mm [inch]
mm [inch]
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F)
Indoor intake air temperature
D.B.
35°C(95°F), W.B. 21.7°C(71°F)
D.B. 19.4°C(67°F), W.B. 13.9°C(57°F)
D.B. 26.7°C(80°F), W.B. 19.4°C(67°F)
D.B. 21.1°C(70°F), W.B. 15.6°C(60°F)
PKA-A12HA4
PKA-A18HA4
PUY-A18NHA4
PUY-A18NHA4-BS
12,000
18,000
12,000
18,000
6,000
8,000
2240
1190
8.0
10.1
15.3
15.2
5.2
2.0
0.68
0.81
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1phase , 60Hz , 208/230V
15
0.33
30
9-10.5-12
8-9.5-11
320-370-425
290-335-380
36-40-43
White Munsell 1.0Y 9.2/0.2
898 [35-3/8]
249 [9-13/16]
295 [11-5/8]
13
29
13
15
20
0.35
40
SNB130FQCM1
14
34 [1,200]
46
48
-
800 [31-1/2]
300+23 [11-13/16 + 7/8]
600 [23-5/8]
37 [82]
40 [89]
1.3 [2 lbs 14 oz]
1.7 [3 lbs 12 oz]
0.65 (MEL56) [20]
12.7 [1/2]
6.35 [1/4]
Max. 30m [Max. 100ft]
PKA-A24KA4
PKA-A30KA4
PUY-A24NHA4
PUY-A30NHA4
PUY-A24NHA4-BS
PUY-A30NHA4-BS
24,000
30,000
24,000
30,000
12,000
12,000
2270
4130
10.6
7.3
17.0
15.5
5.0
8.1
0.77
0.70
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
25
AC 208 / 230V
DC24V
DC12V : Wired type
1
15
0.36
56
18-20-22
16-18-20
635-705-775
570-635-700
0
39-42-45
1170 [46-1/16]
295 [11-5/8]
365 [14-3/8]
21
46
16 [5/8]
Attached in Indoor Unit
18
30
0.75
75
TNB220FLHM
12
55 [1,940]
Linear Expansion Valve
-
48
-
Ivory Munsell 3Y 7.8/1.1
950 [37-3/8]
330+30 [13 + 1-3/16]
943 [37-1/8]
74[163]
R410A
3.0 [6 lbs 10 oz]
0.87 (FV50S) [28]
15.88 [5/8]
9.52 [3/8]
Max. 30m [Max. 100ft]
Max. 50m [Max. 165ft]
Not Supplied
Flared
Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Outdoor intake air temperature
D.B. 46°C(115°F)
D.B. -18°C(0°F)*
D.B. 21.1°C(70°F), W.B. 15°C(59°F)
D.B. -11.1°C(12°F), W.B. -12.2°C(10°F)
PKA-A36KA4
PUY-A36NHA4
PUY-A36NHA4-BS
34,200
34,200
12,000
5030
6.8
14.0
9.2
0.70
-
-
-
-
-
-
-
-
-
30
0.57
20-23-26
18-21-23
705-810-920
635-730-830
43-46-49
25
40
17.5
5