Wiring Diagram - Mitsubishi Electric PLA-A·BA4 Technical Data Manual

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for PLA-A·BA4:
Table of Contents

Advertisement

5

WIRING DIAGRAM

PLA-A12BA4 PLA-A18BA4 PLA-A24BA4 PLA-A30BA4 PLA-A36BA4 PLA-A42BA4
[LEGEND]
SYMBOL
NAME
I.B
INDOOR CONTROLLER BOARD
CN2L
CONNECTOR (LOSSNAY)
CN24
CONNECTOR <BACK-UP HEATING>
CN30
CONNECTOR <LLC>
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROL)
CN105
CONNECTOR (RADIO FREQUENCY INTERFACE)
FUSE
FUSE (T6.3AL250V)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
SW1
SWITCH (MODEL SELECTION)
SW2
SWITCH (CAPACITY CODE)
SWE
CONNECTOR (EMERGENCY OPERATION)
X1
RELAY (DRAIN PUMP)
DP
DRAIN PUMP
FS
DRAIN FLOAT SWITCH
RADIO FREQUENCY INTERFACE FOR RF THERMOSTAT
RFI
<Table 2>SW2 (CAPACITY CODE)
SW2
MODELS
Service
MODELS
1 2 3 4 5
PLA-A12BA4
PLA-A30BA4
ON
OFF
1 2 3 4 5
PLA-A18BA4
PLA-A36BA4
ON
OFF
1 2 3 4 5
PLA-A24BA4
PLA-A42BA4
ON
OFF
The black square (
) indicates a switch position.
I.B
VANE CNV (WHT )
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
WIRELESS
1
3
CN90
CN3G
(WHT )
1
9
(BLK )
9
CNB
5
5
5
5
BZ
LED2
SW1
M
M
M
M
LED1
SW2
MV
MV
MV
MV
RU
W.B
GRILLE
Notes: 1. SymboIs used in wiring diagram above are,
2. Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3 ).
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
1.Use copper supply wires.
30
SYMBOL
MF
FAN MOTOR
MV
VANE MOTOR
TB4
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TB5,TB6
TRANSMISSION LINE)
TH1
ROOM TEMP. THERMISTOR
(32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
TH5
COND. / EVA. TEMP. THERMISTOR
(32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
OPTION PART
See table 1
PCB FOR IR WIRELESS REMOTE CONTROLLER
W.B
See table 2
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE)
RU
RECEIVING UNIT
SW1
EMERGENCY OPERATION (HEAT / DOWN)
SW2
EMERGENCY OPERATION (COOL / UP)
R.B
WIRED REMOTE CONTROLLER BOARD
TB6
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
Service
1 2 3 4 5
Refer to tables 1 and 2
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
2 1
ON
OFF
TB6
R.B
J41
J42
SW1
SW2
CN51 (WHT ) CN24 (YLW )
Pair No.
5
CN41 (WHT )
CN2L
2 1
LED3
LED2
LED1
SWE
ON OFF
I-SEE
I-SEE
CN105
SENSOR
SENSOR MOTOR
CN4Y
CN6Y
(RED )
(WHT )
(RED )
1
4
1
6
1
5
5
5
4
M
I-SEE
RFI
SENSOR
MT
I-SEE SENSOR
CORNER PANEL
(OPTION PART)
: Connector,
NAME
<Table 1>SW1 (MODEL SELECTION)
TB5
SW1
2
Service
1
1 2 3 4 5
TRANSMISSION
WIRES
2
DC12V
CN32
(WHT )
1
3
1 3
INDOOR/OUTDOOR
COMMUNICATION
2
1
1
CN3C
(BLU)
1
2
REMOCON
4
1
CN22
(BLU)
FLOAT SW
LIQUID/PIPE
INTAKE
CN30
CN4F
CN44
CN20
(GRN )
(WHT )
(WHT )
(RED )
1
4
1
4
1 2
1
3
7
FS
TH2
TH5
TH1
Be sure to turn off the source power
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
: Terminal block .
ON
OFF
1 3 5
OUTDOOR
CN01
(BLK)
FUSE
DC280V
RECTIFICATION
X1
FAN
D.U.M
CNMF
CNP
CNAC
(WHT )
4
1
3
1
1
3
(BLU )
(WHT )
M
MS
1~
3~
DP
MF
1
TB4
YLW
YLW
S1
TO
ORN
ORN
S2
OUTDOOR
UNIT
S3
ORN
BRN

Hide quick links: