8-3 Wire connecting the indoor unit terminal blocks

1. Terminal press of Ring terminal shall be set facing up before connecting wire.
2. There shall be no empty space between Ring terminal and Screw after Clamp.
If not, there exists a possibility of fire which can be caused by electric heat in the connecting part.
,
: Good
Bad : Ring terminal is connected reversely
Bad : Not clamped Screw
Bad : In the gap between Ring terminal & Screw
Bad : Unused Ring Terminal
8-8
Is inverted
Terminalhasbeencut.