Recovery Of Refrigerant In Failed Outdoor Unit; In Case Of Failure Of Follower Unit - Toshiba Super MMU-AP0091H Service Manual

Super modular multi
Hide thumbs Also See for Super MMU-AP0091H:
Table of Contents

Advertisement

5-5. Recovery of Refrigerant in Failed Outdoor Unit

(In Case of Failure of Follower Unit)

(MMY-MAP1001H)
TE1
PMV1
PMV2
SV5
Pd sensor
TL
SV3D
Liquid
tank
SV41
HP
SV3E
Strainer
Strainer
PMV
TC2
TCJ
High-pressure gas or condensate liquid refrigerant
Evaporative gas refrigerant (Low-pressure gas)
NOTE
An outdoor unit which is connected with indoor/outdoor communication
lines is the "Header unit", and the other unit is called "Follower unit".
Header unit
FM
TO
4-Way valve
SV2
Ps sensor
OS
SV42
HP
Accumulator
SV3C
TD1
TD2
TK3
TK1
TK2
Oil tank
TK4
SV3A
SV3B
Balance pipe
Liquid pipe
Gas pipe
Gas pipe
Liquid pipe
Strainer
Strainer
PMV
TC1
TC2
TCJ
(MMY-MAP1001H)
Failure
TE1
PMV1
PMV2
TS1
Pd sensor
TL
SV3D
Liquid
tank
1
3
*
*
2
*
1 Packed valve of balance pipe = Open fully
*
2 Packed valve at liquid side = Close fully
*
3
Service valve open fully at gas side
*
Close fully 10 minutes after operation start
Strainer
Strainer
PMV
TC1
TC2
TCJ
Indoor unit
63
Follower unit
FM
TO
4-Way valve
SV5
SV2
Ps sensor
OS
SV41
SV42
HP
HP
SV3C
TD1
TD2
TK3
TK1
TK2
Oil tank
SV3E
TK4
SV3A
SV3B
Strainer
PMV
TC1
TC2
TCJ
(Example: 20HP system)
TS1
Accumulator
Strainer
TC1