Troubleshooting by Remote Controller
4.27 Open Phase or Power Supply Voltage Imbalance
P1
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
The error is detected according to the voltage waveform of main circuit capacitor built in
Detection
inverter.
Error Decision
When the aforementioned voltage waveform becomes identical with the waveform of the power
Conditions
supply open phase.
Supposed
Open phase
Causes
Voltage imbalance between phases
Defective outdoor unit PCB
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Measure the power supply voltage
between 3 phases. (R-S, S-T, T-R)
YES
Is the voltage
rated 10%?
NO
Is the voltage
imbalance between phases
less than ±10%?
YES
174
Defective main circuit capacitor
Power unit (Disconnection in diode module)
Defective magnetic relay (K1R, K10R)
Improper main circuit wiring
YES
NO
ESIE12-06
Field factors
Field factors
Replace the outdoor unit
inverter PCB.
Service Diagnosis