4.10 Set V/F pattern

Purpose
Set motor ratings
Select a V/F pattern according to
applications
Automatically set a V/F pattern for
elevators
Use special motor

4.10.1 Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47, Pr. 113)

Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
Parameter
Name
Number
3
Base frequency
19
Base frequency voltage
47
Second V/F (base frequency)
113
Third V/F (base frequency)
Pr.19
(2) Set multiple base frequencies (Pr. 47, Pr. 113)
⋅ When you want to change the base frequency when switching two motors with one inverter, use the Pr. 47 Second V/F
(base frequency).
⋅ Pr. 47 Second V/F (base frequency) is made valid when the RT signal in ON and Pr. 113 Third V/F (base frequency) is
made valid when the X9 signal is on. Assign the terminal for X9 signal input using any of Pr. 178 to Pr. 189 (input
terminal function selection).
REMARKS
⋅ The RT(X9) signal acts as the second (third) function selection signal and makes the other second (third) functions valid. (Refer
to page 225)
⋅ In the initial setting, the RT signal is assigned to the RT terminal. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
Parameter that must be Set
Base frequency, base
frequency voltage
Load pattern selection
Elevator mode (automatic
acceleration/deceleration)
Adjustable 5 points V/F
Initial Value
Setting Range
60Hz
9999
9999
9999
(1) Setting of base frequency (Pr. 3)
⋅ When operating a standard motor, generally set the rated
frequency of the motor to Pr. 3 Base frequency. When running
the motor using commercial power supply-inverter switch-over
operation, set Pr. 3 to the same value as the power supply
frequency.
⋅ If the frequency given on the motor rating plate is "50Hz" only,
always set to "50Hz". Leaving the base frequency unchanged
Output frequency
from "60Hz" may make the voltage too low and the torque
(Hz)
Pr.3
insufficient. It may result in an inverter trip due to overload.
Pr.47
Special care must be taken when "1" (reduced torque load) is
Pr.113
set in Pr. 14 Load pattern selection.
⋅ When using the Mitsubishi constant-torque motor, set Pr. 3 to
60Hz.
Pr. 3, Pr. 19, Pr. 47, Pr. 113
Pr. 14
Pr. 61, Pr. 64, Pr. 292
Pr. 71, Pr. 100 to Pr. 109
V/F
V/F
V/F
Set the frequency when the motor
0 to 400Hz
rated torque is generated. (50Hz/60Hz)
0 to 1000V
Set the base voltage.
8888
95% of power supply voltage
9999
Same as power supply voltage
Set the base frequency when the RT
0 to 400Hz
signal is on.
9999
Second V/F invalid
Set the base frequency when the X9
0 to 400Hz
signal is ON.
9999
Third V/F is invalid
Set V/F pattern
Refer to Page
155
157
159
160
Description
155
Pr. 2
page 153
Pr.4
page 161
Pr.18
page 153
Pr.20
page 168
Pr.46
page 142
Pr.48
page 148
Pr.112
page 142
Pr.114
page 148