Table 13: Compressor Fault Alarms
Description
Compressor Current Overload Trip #1
Compressor Current Overload Trip #2
High Motor Temperature Comp 1
High Motor Temperature Comp 2
Overvoltage On Compressor 1
Overvoltage On Compressor 2
Undervoltage On Compressor 1
Undervoltage On Compressor 2
High Condenser Pressure Circuit 1
High Condenser Pressure Circuit 2
High Discharge Temperature Circuit 1
High Discharge Temperature Circuit 2
Starter Fault Compressor 1
Starter Fault Compressor 2
No Starter Transition Comp 1
No Starter Transition Comp 2
General Compressor Fault 1
General Compressor Fault 2
Communication Fault 1
Communication Fault 2
Interlock Fault
Interlock Fault 2
www.DaikinApplied.com
OITS Alarm Message
COMPR STOP - Motor Current Overload
COMPR STOP - Motor Current Overload
COMPR STOP - High Motor Temperature
COMPR STOP - High Motor Temperature
COMPR STOP - Line Voltage High
COMPR STOP - Line Voltage High
COMPR STOP - Line Voltage Low
COMPR STOP - Line Voltage Low
COMPR STOP - Condenser Pressure High
COMPR STOP - Condenser Pressure High
COMPR STOP - Discharge Temperature High
COMPR STOP - Discharge Temperature High
COMPR STOP - Compressor Fault
(previously used for WMC general compressor fault)
COMPR STOP - Compressor Fault
(previously used for WMC general compressor fault)
COMPR STOP - Compressor Comm Loss
(previously used for compressor communication error)
COMPR STOP - Compressor Comm Loss
(previously used for compressor communication error)
COMPR STOP - Compressor Fault
COMPR STOP - Compressor Fault
COMPR STOP - Compressor Comm Loss
COMPR STOP - Compressor Comm Loss
NO START - Interlock Fault
NO START - Interlock Fault
45
IOM 1210-1 • MAGNITUDE
o
peraTIon
Alarm Reset
Auto-clears
Auto-clears
Locked off if UL Limit is exceeded
Auto-clears
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Locked off if Tripped 3x in 50 min
Reset is dependent on specific alarm
Reset is dependent on specific alarm
Auto-clears
Auto-clears
Reset is dependent on specific alarm
Reset is dependent on specific alarm
Auto-clears
Auto-clears
Auto-clears
Auto-clears
MODEL WMC CHILLERS
®