ALARMS Setpoints
Figure 29: ALARMS Setpoint Screen
Table 6: ALARMS Setpoint Settings
Description
Condenser Freeze Protect
Evaporator Freeze Protect
Motor Current Threshold
Surge Slope Limit
Surge Temperature Limit
High Discharge Temp-Stop
High Discharge Temp-Load
High Condenser Pressure
Low Evap Pressure, Stop
Low Evap Pressure-Unload
Low Evap Pressure-Inhibit
NOTE: The setpoints listed in
representative for more information.
www.DaikinApplied.com
No .
Default
Range
11
34.0 °F
-9.0 to 45.0 °F
10
34.0 °F
-9.0 to 45.0 °F
9
10%
1 to 20%
8
20 °F/min
1 to 99 deg F/min
7
50 °F
2 to 45 °F
6
190 °F
120 to 240 °F
5
170 °F
120 to 240 °F
4
140 psi
120 to 240 psi
3
26 psi
10 to 45 psi
2
31 psi
20 to 45 psi
1
33 psi
20 to 45 psi
Table 6
should only be changed by a Daikin Applied technician. Contact a Daikin Applied service
Password
T
Minimum condenser saturated temperature to start pump
T
Minimum evaporator saturated temperature to start pump
T
Min %RLA to consider that the is motor off
Surge temperature (ST) slope value above which alarm occurs.
T
T
At start, Surge Temp (ST) is compared to this SP. Alarm at ST>2x SP.
T
Max discharge temp to shut down compressor
T
Sets discharge temp above which a forced capacity increase occurs
T
Max discharge pressure, stop compressor
T
Min evap pressure – stop compressor
T
Min evap pressure – unload compressor
T
Min evap pressure – inhibit loading
29
IOM 1210-1 • MAGNITUDE
Comments
Active only if ST>SP7 at start
MODEL WMC CHILLERS
®