15.3 Programming Of Variable Frequency Drive

Parameter
Parameter
Number
Name
P01
Line Voltage
P03
Start Method
P05
Standard
Speed
Source
P44
Password
P45
Speed at
Minimum
Signal
P46
Speed at
Maximum
Signal
15.3.1 Modulating Thermostat
Turn "OFF" the power to the transformer relay. Using
the procedure described on Page 66, Section 14,
alter the parameters above on the VFD. Turn on the
transformer relay and program the modulating
thermostat to the customer's requirements.
Factory
New
Default
Setting
01
01
01
05
01
(03) (0-10) Vdc
(04) (4-20) mA
225
Any #
000-999
0.0Hz
Frequency
Setting noted
on Page 68,
Section 15.2.2
60.0Hz
Frequency
Setting noted
on Page 68,
Section 15.2.1
SECTION 15: C
T
CORAYVAC
OMMISSIONING
HE
®
M
S
ODULATING
YSTEM