Troubleshooting

6.2
Troubleshooting
6.2.1 Equipment does not operate, or operation lamps does not light.
Caution
1
Models Covered
MC707VM-S
MC707VM-W
2
Method of Mal-
function Detection
3
Malfunction Deci-
sion conditions
4
Supposed Causes
The unit is not turned on.
Unspecified voltage is used.
The safety device is activated due
to poor assembly of the panel.
Front panel switch is defective.
The PCB is defective.
30
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
5
Troubleshooting
Is AC cord plugged in?
Or is breaker "ON"?
Is the panel closed
certainly?
Do other appliances operate?
Is rated voltage within ±10%?
Is operation possible
with remote controller?
Is operation possible with
ON/OFF switch?
Remove panel.
Is protrusion on the rear
panel damaged?
Front panel switch operation check
Press front panel switch with a thin
stick, then press ON/OFF switch
after 5 seconds.
Front panel operation
lamp light?
Diagnosis
No
Yes
No
Yes
No
Is there power failure?
Yes
Is 220-240V supplied?
No
Yes
Yes
(Cannot operate
with ON/OFF switch on unit)
No
Yes
(Cannot operate with remote controller)
No
Yes
No
Yes
No
SiBE81-623A
Remedy
Plug in AC cord.
Set breaker to
"ON".
Close the panel
firmly.
Yes
Wait for power res-
toration.
No
When unspecified
voltage is applied,
No
replace power sup-
ply PCB.
Yes
(Varistor or fuse
may be damaged.)
Contact power
company.
Replace ON/OFF
switch cover.
(Replace display
PCB).
Go to "6.2.2.
Remote controller
sends signals errat-
ically".
Replace panel.
*Protrusion on front
panel switch
Rear side
Protrusion
Replace panel
(front panel switch
is not securely
mounted due to
deformity).
Replace the equip-
ment or the power
supply and control
PCB.
Photocatalytic Air Purifiers